188 Hot- and cold-water supplies<br />

0.5<br />

0.4<br />

Water flow rate (I/s)<br />

0.3<br />

0.2<br />

0.1<br />

0<br />

0 20 40 60 80 100<br />

Demand units<br />

6.6 Simultaneous flow data for water draw-off points.<br />

Table 6.3 Flow of water in copper tube of various diameters.<br />

Δp/EL (N/m 3 )<br />

Water flow rate q (kg/s)<br />

15mm 22mm 28mm 35mm 42mm<br />

1000<br />

1500<br />

2000<br />

2500<br />

3000<br />

v = 1.5<br />

v = 2<br />

0.160<br />

0.201<br />

0.236<br />

0.268<br />

0.296<br />

0.429<br />

0.537<br />

0.630<br />

0.712<br />

0.787<br />

0.933<br />

1.170<br />

1.370<br />

1.540<br />

1.710<br />

1.60<br />

2.00<br />

2.34<br />

2.65<br />

2.92<br />

2.58<br />

3.22<br />

3.77<br />

4.26<br />

4.70<br />

v = 3<br />

v = 4<br />

Note: v = water velocity (m/s).<br />

Source: Reproduced from CIBSE Guide (CIBSE, 1986) by permission of the<br />

Chartered Institution of <strong>Building</strong> <strong>Services</strong> Engineers.<br />

3. Sum all the DU along the pipework to the water source, which will be the storage tank or<br />

incoming water main.<br />

4. Convert DU to water flow rates using Fig. 6.6.<br />

5. Find the head of water H (in metres) causing the flow to each floor level.<br />

6. Estimate the equivalent length (EL) of the pipe run to each floor in metres. This can be taken<br />

as the measured length plus 30% for the frictional resistance of bends, tees and the tap.<br />

7. Find the index circuit. This is the circuit with the lowest ratio of H to EL.<br />

8. Choose pipe sizes from Table 6.3 for the index circuit.<br />

9. Determine the other pipe sizes from the H/EL figure appropriate to each branch of the index<br />

circuit.<br />

10. Determine the water flow rate and head for a bronze-body hot-water service secondary<br />

pump, if one is required.<br />

A notation system can be adopted to gather pipe-sizing data together on drawings, as shown<br />

in Fig. 6.7.