Ventilation and air conditioning 151<br />

Supply air<br />

Condenser coil and<br />

propeller fan in<br />

outside air duct<br />

+<br />

+ Electronic heater<br />

– Refrigeration coil<br />

Drip tray<br />

Fan<br />

Filter<br />

Recirculated room air<br />

Refrigeration compressor<br />

5.15 Packaged air-conditioning unit.<br />

and have a change-over valve to reverse the refrigerant flow direction. This enables the unit to<br />

cool the internal air in summer and the external air in winter.<br />

Heat rejected from the condenser is used to heat the internal environment in winter. In this<br />

mode of operation it is called a heat pump. A separate ventilation system may be needed.<br />

Compressor and fan noise levels are compared with the acceptable background acoustic environment.<br />

Maintenance requirements are filter cleaning, bearing lubrication and replacement of<br />

the compressor when it becomes too noisy or breaks down.<br />

Split system units have a separate condenser installed outside the building. Two refrigerant<br />

pipes of small diameter connect the internal and external equipment boxes. This allows<br />

greater flexibility in siting the noise-producing compressor. Ducted models provide conditioning<br />

and ventilation and are often sited on flat roofs. Figure 5.15 shows a typical through-the-wall<br />

installation.<br />

Vapour-compression refrigeration<br />

The electrically driven vapour-compression refrigeration system is the principal type used. Its rival,<br />

the absorption cycle, burns gas to produce cooling but has a coefficient of performance of<br />

around 1, whereas vapour compression has a coefficient of performance in the range 2–5, and<br />

so it is cheaper to operate. Compressor types are as follows.<br />

1. Single- or multi-cylinder reciprocating piston compressor with spring-loaded valves: domestic<br />

refrigerators and small air conditioners have hermetically sealed motor–compressor units<br />

which are sealed for their service period, that is, about 10 years.<br />

A condensing unit comprises a sealed compressor, a refrigerant condenser, a liquid receiver,<br />

pipework and controls. Refrigerant pipework is installed on site from this unit to a finned<br />

pipe forced-draught air-cooling coil in the air-conditioning system.