Built environment 13<br />

1.3 Thermal comfort data logger (reproduced by courtesy of Mobile Architecture and Built Environment<br />

Laboratory, Deakin University, Geelong).<br />

External environments<br />

Extremes of external climate are mainly of concern to construction workers in severe<br />

environments. There are two main indices: wind chill index (WCI) and heat stress index (HSI).<br />

Wind chill index measures the cooling effect on the body of a moving air stream, given by:<br />

WCI = (10.45 + 10 √ v − v)(33 − t a )<br />

Wind speed v is in metres per second; the equation can be used for values of up to 22.0 m/s<br />

(79 km/h (kilometres per hour)). Frostbite should be avoided if the wind chill index is less than<br />

1400 at an air temperature of −10.0 ◦ C d.b. during a maximum exposure of 30 min. A convenient<br />

use of the wind chill index is to calculate the equivalent wind chill temperature (EWCT), which is<br />

the air temperature, calculated from measured data, that would provide the same chilling effect<br />

but at an air velocity of 1.78 m/s (6.4 km/h):<br />

EWCT = (−0.045WCI + 33) ◦ C<br />

EXAMPLE 1.5<br />

A winter day in northern England has an outdoor air velocity measured as 25.2 km/h (7 m/s)<br />

and the sling psychrometer air temperature showed −2.5 ◦ C d.b. Find the wind chill index<br />

and the equivalent wind chill temperature.