336 Room acoustics<br />

The target room may be adjacent to, or close to, the plant room, or it may not be influenced<br />

by the plant room other than by the transfer of noise through the interconnected air-ductwork<br />

system. Analysis of the ductwork route for noise transfer is calculated separately and is not<br />

covered in this book.<br />

EXAMPLE 14.7<br />

The showroom in Example 14.6 has floor dimensions of 25 m × 10 m and a height of<br />

3.6 m to a suspended tile ceiling. The reverberation time of the showroom is 0.5 s. The<br />

air-conditioning plant room generates a sound pressure level of 39 dB in the roof space.<br />

The acoustic tile ceiling has a sound reduction index of 12 dB. Calculate the sound pressure<br />

level that is produced within the showroom by the air-conditioning plant.<br />

SPL 3 = 39 dB<br />

SRI = 12 dB<br />

S 5 = 250 m 2<br />

T 3 = 0.5 s<br />

V 3 = 25 × 10 × 3.6 m 2<br />

= 900 m 3<br />

SPL 4 = SPL 3 − SRI + 10 log(S 5 ) + 10 × log(T 3 ) − 10 × log(0.16 × V 3 ) dB<br />

= 50 − 12 + 10 × log(250) + 10 × log(0.5) − 10 × log(0.16 × 900) dB<br />

= 50 − 12 + 23 − 3 − 21 dB<br />

= 37 dB<br />

Noise rating<br />

The human ear has a different response to each frequency within the audible range of<br />

20–20 000 Hz. It has been found that a low-frequency noise can be tolerated at a greater sound<br />

pressure level than a high-frequency noise. Noise rating (NR) curves are used to specify the loudness<br />

of sounds. Each curve is a representation of the response of the human ear in the range of<br />

audible frequencies.<br />

The design engineer makes a comparison between the sound pressure level produced in the<br />

room at each frequency and the noise rating curve data at the same frequency. When all the<br />

noise levels within the room fall on or below a noise rating curve, that noise rating is attributed<br />

to the room. Noise rating curves for NR 25 to NR 50 are shown on Fig. 14.3. The values are<br />

plotted from,<br />

SPL = NR f × B f + A f dB<br />

SPL = sound pressure level at frequency f and noise rating NR<br />

NR f = noise rating at frequency f Hz<br />

B f and A f = physical constants<br />

f = frequency<br />

dB<br />

dimensionless<br />

dB<br />

Hz