Room acoustics 339<br />

For 125 Hz,<br />

SPL = 55 × 0.87 + 22 dB<br />

= 69 dB<br />

For 250 Hz,<br />

SPL = 55 × 0.93 + 12 dB<br />

= 63 dB<br />

For 500 Hz,<br />

SPL = 55 × 0.974 + 4.8 dB<br />

= 58 dB<br />

For 1000 Hz,<br />

SPL = 55 × 1.0 + 0dB<br />

= 55 dB<br />

For 2000 Hz,<br />

SPL = 55 × 1.015 − 3.5 dB<br />

= 52 dB<br />

For 4000 Hz,<br />

SPL = 55 × 1.025 − 3.5 dB<br />

= 50 dB<br />

For 8000 Hz,<br />

SPL = 55 × 1.03 − 8.0 dB<br />

= 48 dB<br />

These sound pressure levels are compared to the room data in Table 14.8.<br />

The closest approach to the SPL limit for NR 55 occurs at 500 Hz. Check that NR 50 is exceeded.<br />

For 500 Hz,<br />

SPL = 50 × 0.974 + 4.8 dB<br />

= 53 dB<br />

Table 14.8 Noise spectrum in Example 14.8.<br />

Frequency f (Hz) 31.5 63 125 250 500 1k 2k 4k 8k<br />

NR 55 SPL (dB) 92 78 69 63 58 55 52 50 48<br />

Room SPL (dB) 39 44 48 52 55 49 36 33 28