Heating 97<br />

6. Choose pipe sizes from a chart or data, using an estimate of pressure loss rate and maximum<br />

allowable water velocity.<br />

7. Calculate the pump head and water flow rate; compare with the pump manufacturer’s<br />

stated performance curves and choose a suitable pump.<br />

The temperature of water flowing through a heat emitter or along a pipe will drop from its<br />

flow temperature t f ◦ C to its return temperature t r ◦ C and lose heat Q W. If there is one heater in a<br />

room, Q will be equal to the room steady-state heat loss. Heat losses from distribution pipework<br />

may initially be assumed to be 10% of the room heat loss, and the radiator water flow rate<br />

should be increased by this amount.<br />

The specific heat capacity (SHC) of water is 4.19 kJ/kgK. The heat balance equation is:<br />

heat lost by water = radiator heat output Q + pipe heat loss<br />

or<br />

water flow rate q × SHC × temperature drop = Q + 10% × Q<br />

water flow rate q =<br />

1.1 Q<br />

SHC(t f − t r ) kg/s<br />

The radiator manufacturer’s heat output data will be for a fixed temperature difference<br />

between the mean water temperature and the room air temperature. Usually a figure of 55 K<br />

is used. Comparison of design conditions and literature data can be made using the following<br />

equations:<br />

radiator mean water temperature MWT = t f + t r<br />

2<br />

room heat loss<br />

radiator heat output at 55 K difference =<br />

temperature correction factor<br />

where:<br />

[ ] ((tf + t r )/2) − t 1.30 a<br />

temperature correction factor =<br />

55<br />

and t a is the room air temperature ( ◦ C).<br />

EXAMPLE 4.1<br />

A double-panel radiator is to be installed in a room where the air temperature is 22 ◦ C<br />

and the heat loss is 4250 W. Water flow and return temperatures are to be 82 ◦ C and<br />

71 ◦ C respectively. An extract from a radiator manufacturer’s catalogue for a temperature<br />

difference of 55 K is given in Table 4.2. Select a suitable radiator and find the water flow<br />

rate through it.