Error Codes 110/149<br />
Status & Error Codes TCP_<strong>IP</strong>-Task<br />
Error Code (Definition) Value Description<br />
TLR_E_TCP_TASK_F_ MESSAGESIZE 0xC0080097 The packet length parameter ulLen is<br />
invalid. The correct packet lenght depends<br />
on the command parameter ulCmd.<br />
TLR_E_TCP_TASK_F_ MESSAGECOMMAND 0xC0080098 The command ulCmd is unknown.<br />
TLR_E_TCP_TASK_F_<br />
MESSAGECOMMANDRUNNING<br />
0xC008009E The command cannot be executed,<br />
because the previous command is still<br />
running.<br />
TLR_E_TCP_TASK_F_NOT_ INITIALIZED 0xC00800C8 The task is not initialized.<br />
TLR_E_TCP_TASK_F_BUSY 0xC00800C9 The task is busy (intern).<br />
TLR_E_TCP_TASK_F_ DATABASE 0xC00800D2 The configuration database is not<br />
available.<br />
TLR_E_TCP_TASK_F_ DATABASE_READ 0xC00800D4 Error while reading configuration database.<br />
TLR_E_<strong>IP</strong>_ERR_<strong>IP</strong>_ADDR_<br />
0xC0070100 The <strong>IP</strong> address parameter ulIpAddr in<br />
INVALID_<strong>IP</strong>_CMD_PING<br />
command TCP<strong>IP</strong>_<strong>IP</strong>_CMD_PING_REQ is<br />
invalid. This means, the <strong>IP</strong> address<br />
ulIpAddr is equal to the TCP/<strong>IP</strong> stacks own<br />
<strong>IP</strong> address.<br />
TLR_E_TCP_ERR_<strong>IP</strong>_ADDR_<br />
0xC0080101 The <strong>IP</strong> address parameter ulIpAddr in<br />
INVALID_TCP_UDP_CMD_ OPEN<br />
command<br />
TCP<strong>IP</strong>_TCP_UDP_CMD_OPEN_REQ is<br />
invalid. The parameter ulIpAddr must be<br />
zero (0.0.0.0) or equal to the TCP/<strong>IP</strong><br />
stacks own <strong>IP</strong> address.<br />
TLR_E_TCP_ERR_<strong>IP</strong>_ADDR_<br />
0xC0080102 The <strong>IP</strong> address parameter ulIpAddr in<br />
INVALID_TCP_CMD_ CONNECT<br />
command<br />
TCP<strong>IP</strong>_TCP_CMD_CONNECT_REQ is<br />
invalid. The parameter ulIpAddr must be<br />
unequal to the TCP/<strong>IP</strong> stacks own <strong>IP</strong><br />
address.<br />
TLR_E_TCP_ERR_<strong>IP</strong>_ADDR_<br />
0xC0080103 The <strong>IP</strong> address parameter ulIpAddr in<br />
INVALID_UDP_CMD_SEND<br />
command<br />
TCP<strong>IP</strong>_UDP_CMD_SEND_REQ is invalid<br />
or doesn't match to the local sub network.<br />
This error occurs, if the <strong>IP</strong> address is zero<br />
(0.0.0.0) or equal to the address of the<br />
local subnet.<br />
TLR_E_TCP_ERR_<strong>IP</strong>_ADDR_I<br />
0xC0080104 The parameter ulMulticastGroup (ulMode<br />
NVALID_TCP_UDP_CMD_ SET_SOCK_OPTION<br />
= TCP_SOCK_ADD_MEMBERSH<strong>IP</strong> or<br />
TCP_SOCK_DROP_MEMBERSH<strong>IP</strong>) in<br />
command<br />
TCP<strong>IP</strong>_TCP_UDP_CMD_SET_SOCK_<br />
OPTION_REQ is invalid. The parameter<br />
ulMulticastGroup must be a valid Multicast<br />
address. Valid Multicast addresses are<br />
224.0.0.1 ... 239.255.255.255 (224.0.0.0 is<br />
reserved as Base-multicast address).<br />
TLR_E_TCP_ERR_PORT_<br />
0xC0080110 The port parameter ulPort in command<br />
INVALID_TCP_UDP_CMD_ OPEN<br />
TCP<strong>IP</strong>_TCP_UDP_CMD_OPEN_REQ is<br />
invalid or not available. The parameter<br />
ulPort must be in range 0 ... 65535.<br />
TLR_E_TCP_ERR_PORT_ INVALID_TCP_CMD_ 0xC0080111 The port parameter ulPort in command<br />
CONNECT<br />
TCP<strong>IP</strong>_TCP_CMD_CONNECT_REQ is<br />
invalid or not available. The parameter<br />
ulPort must be in range 1 ... 65535.<br />