Error Codes 123/149<br />
9.5.1 C<strong>IP</strong> Connection-Manager-Object-Instance Codes zum<br />
Erweiterten Status<br />
Additionally to the General C<strong>IP</strong> Error Codes the C<strong>IP</strong> Connection Manager<br />
Object Instance Extended Status Codes are valid.<br />
C<strong>IP</strong> Connection Manager Object Instance Extended Status Codes<br />
General Status Extended Description<br />
(hexa decimal) Status<br />
0x00 Service completed successfully<br />
0x01 0x0000<br />
through<br />
0x00FF<br />
Obsolete<br />
0x01 0x0100 CONNECTION IN USE OR DULTPLICATE FORWARD OPEN<br />
This extended status code shall be returned when an originator is trying to make<br />
connection to a target with which the originator may have already established a<br />
connection (Non-Null/matching Forward_Open — see section 3-5.5.2.1.2).<br />
[Ref.] THE C<strong>IP</strong> NETWORKS LIBRARY, Volume 1<br />
0x01 0x0101<br />
through<br />
0x0102<br />
Reserved by C<strong>IP</strong><br />
0x01 0x0103 TRANSPORT CLASS AND TRIGGER COMBINATION NOT SUPPORTED<br />
A transport class and trigger combination has been specified which is not<br />
supported by the target. Routers shall not fail the connection based on the<br />
transport class and trigger combination. Only targets shall return this extended<br />
status code.<br />
0x01 0x0104<br />
through<br />
0x0105<br />
Reserved by C<strong>IP</strong><br />
0x01 0x0106 OWNERSH<strong>IP</strong> CONFLICT<br />
The connection cannot be established since another connection has exclusively<br />
allocated some of the resources required <strong>for</strong> this connection. An example of this<br />
would be that only one exclusive owner connection can control an output point on<br />
an I/O Module. If a second exclusive owner connection (or redundant owner<br />
connection) is attempted, this error shall be returned. This extended status code<br />
shall only be returned by a target node.<br />
0x01 0x0107 TARGET CONNECTION NOT FOUND<br />
This extended status code shall be returned in response to the <strong>for</strong>ward_close<br />
request, when the connection that is to be closed is not found at the target node.<br />
This extended status code shall only be returned by a target node. Routers shall<br />
not generate this extended status code. If the specified connection is not found at<br />
the intermediate node, the close request shall still be <strong>for</strong>warded using the path<br />
specified in the Forward_Close request.<br />
0x01 0x0108 INVALID NETWORK CONNECTION PARAMETER<br />
This extended status code shall be returned as the result of specifying a<br />
connection type, connection priority, redundant owner or fixed / variable that is not<br />
supported by the target application. Only a target node shall return this extended<br />
status code.<br />
0x01 0x0109 INVALID CONNECTION SIZE<br />
This extended status code is returned when the target or router does not support<br />
the specified connection size. This could occur at a target because the size does<br />
not match the required size <strong>for</strong> a fixed size connection. It could occur at a router if<br />
the requested size is too large <strong>for</strong> the specified network.<br />
An additional status may follow indicating the maximum connection size supported<br />
by the responding node. The additional status word is required when issued in<br />
response to the Large_Forward_Open.<br />
<strong>DTM</strong> <strong>for</strong> <strong>EtherNet</strong>/<strong>IP</strong> <strong>Scanner</strong> <strong>Devices</strong> | Configuration of <strong>EtherNet</strong>/<strong>IP</strong> <strong>Scanner</strong> <strong>Devices</strong><br />
DOC061201OI06EN | Revision 6 | English | 2010-08 | Released | Public © <strong>Hilscher</strong>, 2006-2010