Error Codes 128/149<br />
C<strong>IP</strong> Connection Manager Object Instance Extended Status Codes<br />
General Status<br />
(hexa decimal)<br />
Extended<br />
Status<br />
Description<br />
0x01 0x031E NO MORE USER CONFIGURABLE LINK CONSUMER RESOURCES<br />
AVAILABLE IN THE PRODUCING MODULE<br />
A target shall return this extended status when the configured number of<br />
consumers <strong>for</strong> a producing application is already in use.<br />
0x01 0x031F NO MORE USER CONFIGURABLE LINK CONSUMER RESOURCES<br />
AVAILABLE IN THE PRODUCING MODULE<br />
A target shall return this extended status when there are no consumers configured<br />
<strong>for</strong> a producing application to use.<br />
0x01 0x0320<br />
0x07FF<br />
Vendor specific<br />
0x01 0x0800 Network link in path to module is offline<br />
0x01 0x0801<br />
through<br />
0x080F<br />
Reserved by C<strong>IP</strong><br />
0x01 0x0810 NO TARGET APPLICATION DATA AVAILABLE<br />
This extended status code is returned when the target application does not have<br />
valid data to produce <strong>for</strong> the requested connection, Only the target side of a<br />
connection shall return this extended status code.<br />
0x01 0x0811 NO ORIGNATOR APPLICATION DATA AVAILABLE<br />
This extended status code is returned when the originator application does not<br />
have valid data to produce <strong>for</strong> the requested connection. Only the originator side<br />
of connection shall indicate this extended status code.<br />
0x01 0x0812 NODE ADDRESS HAS CHANGED SINCE THE NETWORK WAS SCHEDULED<br />
A router on a scheduled network (e.g.: ControlNet) has a different node address<br />
than the value configured in the connection originator.<br />
0x01 0x0813 NOT CONFIGURED FOR OFF-SUBNET MULTICAST<br />
A multicast connection has been requested between a producer and a consumer<br />
that are on different subnets, and the producer is not configured <strong>for</strong> off-subnet<br />
multicast.<br />
0x01 0x0814 INVALID PRODUCE/CONSUME DATA FORMAT<br />
In<strong>for</strong>mation in the data segment indicates that the <strong>for</strong>mat of the produced and/or<br />
consumed data is not valid.<br />
0x01 0x0815<br />
through<br />
0xFCFF<br />
Reserved by C<strong>IP</strong><br />
0x09 Index to ERROR IN DATA SEGMENT<br />
Element<br />
This general status code shall be returned when there is an error in the data<br />
segment of a <strong>for</strong>ward open.<br />
The Extended Status shall be the index to where the error was encountered in the<br />
Data Segment (Reference section C-1.4.5 — DATA SEGMENT).<br />
[Ref.] THE C<strong>IP</strong> NETWORKS LIBRARY, Volume 1<br />
0x0C Optional OBJECT STATE ERROR<br />
This general status code shall be returned when the state of the target object of<br />
the connection prevents the service request from being handled. The Extended<br />
Status reports the object’s present state. The extended status is optional.<br />
For example, a target (application) object of the connection may need to be in an<br />
edit mode be<strong>for</strong>e attributes can be set. This is different from a service being<br />
rejected due to the state of the device.<br />
<strong>DTM</strong> <strong>for</strong> <strong>EtherNet</strong>/<strong>IP</strong> <strong>Scanner</strong> <strong>Devices</strong> | Configuration of <strong>EtherNet</strong>/<strong>IP</strong> <strong>Scanner</strong> <strong>Devices</strong><br />
DOC061201OI06EN | Revision 6 | English | 2010-08 | Released | Public © <strong>Hilscher</strong>, 2006-2010