Configuration 49/149<br />

4.3 Scanlist<br />

The Scanlist dialog page shows the list of all configured connections to<br />

<strong>EtherNet</strong>/<strong>IP</strong> adapters used in the <strong>EtherNet</strong>/<strong>IP</strong> <strong>Scanner</strong> configuration.<br />

The <strong>IP</strong> addresses of the <strong>EtherNet</strong>/<strong>IP</strong> adapter station can be edited or set<br />

here.<br />

Figure 26: Configuration > Scanlist<br />

Parameter Meaning Range of Value /<br />

Value<br />

Activate Checkbox, to activate / deactivate a connection.<br />

If the Activate checkbox is checked, process memory in the<br />

controller is reserved <strong>for</strong> this connection and the controller<br />

makes a data exchange on the bus to the corresponding<br />

device/module.<br />

If the Activate checkbox is unchecked, the controller reserves<br />

memory in the process data image <strong>for</strong> this connection, but no<br />

data exchange to the corresponding device/module is made<br />

on the bus.<br />

<strong>IP</strong> Address <strong>IP</strong> address of the <strong>EtherNet</strong>/<strong>IP</strong> adapter station.<br />

valid <strong>IP</strong> address<br />

(editable)<br />

The <strong>IP</strong> address of the <strong>EtherNet</strong>/<strong>IP</strong> Adapter station is set here<br />

in the Scanlist. In the <strong>EtherNet</strong>/<strong>IP</strong> Adapter <strong>DTM</strong> it is only<br />

displayed.<br />

The <strong>EtherNet</strong>/<strong>IP</strong> <strong>Scanner</strong> device transmits the <strong>IP</strong> address of<br />

the <strong>EtherNet</strong>/<strong>IP</strong> Adapter during startup via the <strong>EtherNet</strong>/<strong>IP</strong><br />

network to the <strong>EtherNet</strong>/<strong>IP</strong> Adapter and thereby configures the<br />

<strong>EtherNet</strong>/<strong>IP</strong> Adapter.<br />

Description Symbolic name of the <strong>EtherNet</strong>/<strong>IP</strong> adapter device.<br />

Slot Slot in chassis, <strong>for</strong> modular adapters<br />

Connection<br />

name<br />

Textual connection name<br />

RPI(ms) Requested Packet Rate in ms of a connection<br />

0,001 - 4294967<br />

The fixed point <strong>for</strong>mat can be used <strong>for</strong> values in the<br />

microsecond range, <strong>for</strong> e.g. 0.2 <strong>for</strong> 200 microseconds.<br />

Default: 100<br />

Timeout The Connection Timeout Multiplier specifies the multiplier Value / Multiplier<br />

Multiplier applied to the expected packet rate to obtain the connection<br />

timeout value.<br />

<strong>Devices</strong>/modules shall stop transmitting on a connection<br />

whenever the connection times out even if the pending close<br />

0 / x4 (Default)<br />

1 / x8<br />

2 / x16<br />

has been sent.<br />

Table 19: Device Table Page Parameters<br />

3 / x32<br />

4 / x64<br />

5 / x128<br />

6 / x256<br />

7 / x512<br />

8 - 255 / Reserved<br />