Configuration 49/149<br />
4.3 Scanlist<br />
The Scanlist dialog page shows the list of all configured connections to<br />
<strong>EtherNet</strong>/<strong>IP</strong> adapters used in the <strong>EtherNet</strong>/<strong>IP</strong> <strong>Scanner</strong> configuration.<br />
The <strong>IP</strong> addresses of the <strong>EtherNet</strong>/<strong>IP</strong> adapter station can be edited or set<br />
here.<br />
Figure 26: Configuration > Scanlist<br />
Parameter Meaning Range of Value /<br />
Value<br />
Activate Checkbox, to activate / deactivate a connection.<br />
If the Activate checkbox is checked, process memory in the<br />
controller is reserved <strong>for</strong> this connection and the controller<br />
makes a data exchange on the bus to the corresponding<br />
device/module.<br />
If the Activate checkbox is unchecked, the controller reserves<br />
memory in the process data image <strong>for</strong> this connection, but no<br />
data exchange to the corresponding device/module is made<br />
on the bus.<br />
<strong>IP</strong> Address <strong>IP</strong> address of the <strong>EtherNet</strong>/<strong>IP</strong> adapter station.<br />
valid <strong>IP</strong> address<br />
(editable)<br />
The <strong>IP</strong> address of the <strong>EtherNet</strong>/<strong>IP</strong> Adapter station is set here<br />
in the Scanlist. In the <strong>EtherNet</strong>/<strong>IP</strong> Adapter <strong>DTM</strong> it is only<br />
displayed.<br />
The <strong>EtherNet</strong>/<strong>IP</strong> <strong>Scanner</strong> device transmits the <strong>IP</strong> address of<br />
the <strong>EtherNet</strong>/<strong>IP</strong> Adapter during startup via the <strong>EtherNet</strong>/<strong>IP</strong><br />
network to the <strong>EtherNet</strong>/<strong>IP</strong> Adapter and thereby configures the<br />
<strong>EtherNet</strong>/<strong>IP</strong> Adapter.<br />
Description Symbolic name of the <strong>EtherNet</strong>/<strong>IP</strong> adapter device.<br />
Slot Slot in chassis, <strong>for</strong> modular adapters<br />
Connection<br />
name<br />
Textual connection name<br />
RPI(ms) Requested Packet Rate in ms of a connection<br />
0,001 - 4294967<br />
The fixed point <strong>for</strong>mat can be used <strong>for</strong> values in the<br />
microsecond range, <strong>for</strong> e.g. 0.2 <strong>for</strong> 200 microseconds.<br />
Default: 100<br />
Timeout The Connection Timeout Multiplier specifies the multiplier Value / Multiplier<br />
Multiplier applied to the expected packet rate to obtain the connection<br />
timeout value.<br />
<strong>Devices</strong>/modules shall stop transmitting on a connection<br />
whenever the connection times out even if the pending close<br />
0 / x4 (Default)<br />
1 / x8<br />
2 / x16<br />
has been sent.<br />
Table 19: Device Table Page Parameters<br />
3 / x32<br />
4 / x64<br />
5 / x128<br />
6 / x256<br />
7 / x512<br />
8 - 255 / Reserved<br />