4. WIRING<br />

(5) Wiring the Remote Flowtube (General-<br />

Purpose Use, Submersible Type, Size 500<br />

to 1000 mm (20 to 40 in.)) with Converters<br />

1) Connection with the <strong>AXF</strong>A11 converter<br />

Connect wiring as shown in the figure below.<br />

IMPORTANT<br />

A remote flowtube (size 1100 to 2600 mm)<br />

cannot be combined with <strong>AXF</strong>A14 converter.<br />

(7) Grounding<br />

FUSE<br />

2.5A 250V<br />

Shortbar<br />

I+ I– SO1+ SO2+ COM AL+ AL– C SA A B SB<br />

CURRENT OUT STATUS OUT ALARM OUT<br />

SIGNAL<br />

4-20mA out<br />

N/– L/+ EX1 EX2 P+ P– SI1+ SI2+ COM<br />

POWER SUPPLY EXCIT ATION PULSE OUT STATUS IN<br />

<strong>AXF</strong>A11 converter<br />

CAUTION<br />

A<br />

B<br />

C<br />

Excitation<br />

cable<br />

EX2<br />

Figure 4.2.17 Wiring Diagram<br />

IMPORTANT<br />

<strong>AXF</strong>C dedicated<br />

signal cable<br />

Converter<br />

SA<br />

A<br />

B<br />

SB<br />

C<br />

EX1<br />

EX2<br />

Remote<br />

flowtube<br />

Taping*<br />

A<br />

B<br />

Taping*<br />

C<br />

EX1<br />

EX2<br />

* Individually tape and insulate<br />

the shields corresponding to SA<br />

EX1 and SB on the remote flowtube<br />

side.<br />

Remote flowtube<br />

F040217.EPS<br />

A remote flowtube (size 500 to 1000 mm) cannot<br />

be combined with <strong>AXF</strong>A14 converter.<br />

Be sure to connect the protective grounding of<br />

the <strong>AXF</strong> remote flowtube with a cable of 2mm 2<br />

or larger cross section in order to avoid electrical<br />

shock to the operators and maintenance engineers<br />

and to prevent the influence of external<br />

noise.<br />

Connect the grounding wire to the mark.<br />

The grounding should satisfy Class D requirements<br />

(ground resistance, 100 or less).<br />

In case of TIIS Flameproof type, the grounding<br />

should satisfy Class C requirements (ground<br />

resistance, 10 or less) or class A requirements<br />

(ground resistance, 10 or less).<br />

For explosion proof type except TIIS, follow the<br />

domestic electrical requirements as regulated in<br />

each country.<br />

(6) Wiring the Remote Flowtube (General-<br />

Purpose Use, Submersible Type, Size 1100<br />

to 2600 mm (44 to 104 in.)) with Converters<br />

1) Connection with the <strong>AXF</strong>A11 converter<br />

Connect wiring as shown in the figure below.<br />

IMPORTANT<br />

Improper grounding can have an adverse affect<br />

on the flow measurement. Ensure that the<br />

instrument is properly grounded.<br />

FUSE<br />

2.5A 250V<br />

Shortbar<br />

A<br />

B<br />

C<br />

I+ I–<br />

CURRENT OUT<br />

4-20mA out<br />

N/– L/+<br />

POWER SUPPLY<br />

SO1+ SO2+ COM<br />

STATUS OUT<br />

EX1 EX2<br />

EXCIT ATION<br />

AL+ AL– C SA A B SB<br />

ALARM OUT<br />

SIGNAL<br />

P+ P– SI1+ SI2+ COM<br />

PULSE OUT STATUS IN<br />

<strong>AXF</strong>A11 converter<br />

<strong>AXF</strong>C dedicated<br />

signal cable<br />

Excitation<br />

cable<br />

Remote<br />

Converter<br />

flowtube<br />

SA Taping*<br />

A<br />

A<br />

B<br />

B<br />

SB Taping*<br />

EX2<br />

C<br />

C<br />

EX1 EX1<br />

EX2 EX2<br />

* Individually tape and insulate<br />

the shields corresponding to SA<br />

EX1 and SB on the remote flowtube<br />

side.<br />

Remote flowtube<br />

F040218.EPS<br />

Figure 4.2.18 Wiring Diagram<br />

4-14<br />

IM 01E20D01-01E