Chapter 8, Removal<br />
Removal for shaft fastening by tension bolt<br />
1. Detach the cap (Figure 38/2) from the fan impeller shroud.<br />
2. Detach the front end shield from the generator. For this purpose, unscrew the<br />
four fastening screws (Figure 38/5) of the front end shield at the generator.<br />
3. Hold the engine shaft using the special tool of the engine manufacturer.<br />
4. Undo the tension bolt (Figure 38/1) <strong>and</strong> pull it out of the generator shaft.<br />
5. Insert the pushing rod (Figure 38/3) into the generator shaft instead of the<br />
tension bolt <strong>and</strong> then screw the pushing screw (Figure 38/4) into the<br />
generator shaft. By screwing in the pushing screw, the generator shaft is<br />
detached from the engine shaft.<br />
6. Detach the generator from the engine.<br />
7. Remove the pushing rod (Figure 38/3) <strong>and</strong> the pushing screw (Figure 38/4)<br />
from the generator shaft. Remount the cap (Figure 38/2) onto the fan<br />
impeller shroud.<br />
8. Remove the front end shield (Figure 39/1) of the generator which is still<br />
mounted to the engine. For this purpose, unscrew the four screws (Figure 39/<br />
2) <strong>and</strong> detach the end shield.<br />
9. Remount the front end shield to the generator.<br />
5<br />
1<br />
2<br />
3<br />
4<br />
Figure 38<br />
Removal of brushless single-bearing generators with tension bolt<br />
(1)<br />
Issue date: August 2002 101