Chapter 4: 4.7 Installation of two-bearing generators (<strong>BG</strong> <strong>160</strong>)<br />
4.7 Installation of two-bearing generators (<strong>BG</strong> <strong>160</strong>)<br />
For installing generators of the size <strong>BG</strong> <strong>160</strong> proceed according to the<br />
descriptions in this section 4.7. Prior to installation, read <strong>and</strong> underst<strong>and</strong> the<br />
safety precautions in section 4.1 as well as the sections 4.2 to 4.4 <strong>and</strong> observe<br />
the instructions <strong>and</strong> information given there.<br />
CAUTION<br />
On both sides of the generator, a lifting eye bolt is provided for<br />
attaching lifting equipment. Lifting equipment may only be<br />
attached to the generator using these lifting eye bolts. Only<br />
appropriate lifting equipment may be used.<br />
4.7.1 Dimensions <strong>and</strong> mounting (<strong>BG</strong> <strong>160</strong>)<br />
The minimum clearances <strong>and</strong> regulations for cooling given in section 4.7.2 must<br />
be met for installation. The dimensions of the generator can be found in the<br />
drawing sheet included in the annex.<br />
The generator has to be fastened using<br />
four screws (min. requirements: M12 or<br />
comparable, quality 8.8). The fastening<br />
must be durable as well as shock <strong>and</strong><br />
vibration resistant. The screws must be<br />
secured against self-acting unscrewing by<br />
suitable measures, e.g. a clamp collar<br />
according to DIN 128.<br />
4 fastening screws<br />
• Tightening torque for fastening screws:<br />
M = 87 Nm<br />
Fr max<br />
• Permissible load on the shaft:<br />
Fa max<br />
Fr max = 5000 N (measured at an axial<br />
distance of 60 mm from the shaft<br />
outlet in the end shield)<br />
Fa max = 500 N<br />
No other parts may be mounted to the mounting<br />
profiles of the generator housing.<br />
CAUTION<br />
62 Issue date: August 2002