Chapter 5, Operation<br />

Proceed as follows to take the generator into operation <strong>and</strong> to connect the<br />

loads:<br />

1. If necessary, perform the daily check of the insulation monitoring unit. See<br />

section 5.6.3 on page 84.<br />

2. Make sure that no devices are connected to the generator.<br />

3. Switch off all devices which are to be connected later (switch in position<br />

"OFF" or "0"). Accident hazard by unsupervised starting devices!<br />

4. Start the engine. Wait until the engine has reached its rated speed.<br />

5. If necessary, switch on the circuit breakers in the control box (if equipped,<br />

see Figure 27) or in the control cabinet (position "ON" or "I").<br />

6. Connect (or switch on) the devices one after the other. First switch on the<br />

powerful devices with high current consumptions or high starting currents<br />

<strong>and</strong> then the less powerful devices.<br />

NOTE<br />

The total length of all connected extension cables may not<br />

exceed the following values:<br />

• 250 m max. at a conductor cross section of 2.5 mm 2<br />

• 100 m max. at a conductor cross section of 1.5 mm 2<br />

Devices driven by electric motors possibly require starting<br />

currents that are many times higher than the specified<br />

operating currents. In case of doubt, please contact the<br />

manufacturer.<br />

To ensure a safe operation of three-phase generators, the load<br />

currents should be distributed to all three phases as equal as<br />

possible.<br />

Take care that the maximum currents specified for each socket<br />

are not exceeded.<br />