Chapter 5, Operation<br />

5.6.2 Current distribution <strong>and</strong> connection of devices<br />

DANGER<br />

CAUTION<br />

NOTE<br />

The generator must not be used for the supply of assemblies<br />

for construction sites.<br />

<strong>Generators</strong> which are equipped with an insulation monitoring<br />

unit must not be connected to further insulation monitoring<br />

units since the insulation monitoring units can mutually<br />

interact.<br />

The generator may not be overloaded. The total power consumption<br />

of all connected devices must not exceed the output power<br />

specified for the generator.<br />

Only those devices may be connected the voltage <strong>and</strong> frequency<br />

specifications of which meet the specifications listed on the type<br />

plate of the generator.<br />

If your generator is equipped with a control box:<br />

• Do not use the circuit breakers in the control box for switching<br />

the connected devices on <strong>and</strong> off. When using several devices<br />

connected to the single-phase AC voltage sockets at the same<br />

time (especially when using devices with different power<br />

consumptions), short-term over- or undervoltages may arise due<br />

to a turn-on delay of the neutral conductor.<br />

• The cover of the control box <strong>and</strong> the hinged lids of unused<br />

sockets have always to be kept correctly closed in order to<br />

guarantee IP54 protection (tighten the locking screws by<br />

h<strong>and</strong>).<br />

Current-operated earth-leakage circuit breakers are not functional<br />

in ungrounded networks (IT systems, as supplied by the generator),<br />

because there is no grounding. However, since the generator<br />

supplies the protective measure "protection separation", additional<br />

protection by means of current-operated earth-leakage circuit<br />

breakers is not necessary.<br />

Issue date: August 2002 81