<strong>Synchronous</strong> <strong>Generators</strong> <strong>BG</strong> <strong>132</strong> / <strong>BG</strong> <strong>160</strong><br />
Chapter 5, Operation<br />
5.6.2 Current distribution <strong>and</strong> connection of devices<br />
DANGER<br />
CAUTION<br />
NOTE<br />
The generator must not be used for the supply of assemblies<br />
for construction sites.<br />
<strong>Generators</strong> which are equipped with an insulation monitoring<br />
unit must not be connected to further insulation monitoring<br />
units since the insulation monitoring units can mutually<br />
interact.<br />
The generator may not be overloaded. The total power consumption<br />
of all connected devices must not exceed the output power<br />
specified for the generator.<br />
Only those devices may be connected the voltage <strong>and</strong> frequency<br />
specifications of which meet the specifications listed on the type<br />
plate of the generator.<br />
If your generator is equipped with a control box:<br />
• Do not use the circuit breakers in the control box for switching<br />
the connected devices on <strong>and</strong> off. When using several devices<br />
connected to the single-phase AC voltage sockets at the same<br />
time (especially when using devices with different power<br />
consumptions), short-term over- or undervoltages may arise due<br />
to a turn-on delay of the neutral conductor.<br />
• The cover of the control box <strong>and</strong> the hinged lids of unused<br />
sockets have always to be kept correctly closed in order to<br />
guarantee IP54 protection (tighten the locking screws by<br />
h<strong>and</strong>).<br />
Current-operated earth-leakage circuit breakers are not functional<br />
in ungrounded networks (IT systems, as supplied by the generator),<br />
because there is no grounding. However, since the generator<br />
supplies the protective measure "protection separation", additional<br />
protection by means of current-operated earth-leakage circuit<br />
breakers is not necessary.<br />
Issue date: August 2002 81