<strong>Synchronous</strong> <strong>Generators</strong> <strong>BG</strong> <strong>132</strong> / <strong>BG</strong> <strong>160</strong><br />

Chapter 4: 4.7 Installation of two-bearing generators (<strong>BG</strong> <strong>160</strong>)<br />

The belt must not sag loosely.<br />

When using slim SPA-type V-belts, the<br />

distance between the shafts must not<br />

exceed 800 mm. Permissible shaft distances<br />

for other belts can be obtained from the<br />

manufacturer.<br />

Maximum tractive force (tension) of the<br />

drive belt on the shaft:<br />

F max. = 5000 N at an axial distance of max.<br />

60 mm from the shaft outlet in the end<br />

shield. If the belt is to be mounted with a<br />

greater distance to the end shield, the belt<br />

tension must be reduced in order to<br />

compensate the higher leverage to the<br />

shaft.<br />

F max<br />

l max<br />

Type <strong>and</strong> number of used belts<br />

The type <strong>and</strong> number of used belts have to<br />

be adapted to the power of the generator.<br />

The maximum belt tension force has to be<br />

observed!<br />

Issue date: August 2002 65