Chapter 4: 4.6 Installation of two-bearing generators (<strong>BG</strong> <strong>132</strong>)<br />

Minimum clearances (<strong>BG</strong> <strong>132</strong>, twobearing<br />

types)<br />

The following minimum clearances towards<br />

parts or walls have to be observed for<br />

installation (see also the accompanying<br />

figures on the right):<br />

• Both sides <strong>and</strong> top: a = 100 mm<br />

• Front side: b = 200 mm<br />

• Rear side: c = 170 mm<br />

Cooling (<strong>BG</strong> <strong>132</strong>, two-bearing types)<br />

It is absolutely important to observe the<br />

following regulations for cooling. Danger<br />

of overheating!<br />

The temperature of the supplied cooling air<br />

must not exceed 40 °C.<br />

In the cooling air intake area on the rear<br />

side of the generator a maximum partial<br />

vacuum of P max = 4 Pa may arise.<br />

Otherwise the fan impeller cannot suck<br />

enough cooling air.<br />

In the cooling air blow out area on the<br />

front side of the generator a maximum<br />

overpressure of P max = 7 Pa may arise.<br />

Otherwise the circulation of the cooling air<br />

is not sufficient.<br />

Cooling air circulation must not be<br />

impaired by other air flows (e.g.<br />

directed from the side or from the front<br />

to the generator).<br />

a<br />

a<br />

b<br />

b<br />

P max = 7 Pa<br />

c<br />

a<br />

P max = 4 Pa<br />