Chapter 8, Removal<br />

8.3.1 Removal of single-bearing brush-type generators<br />

Work prior to removal <strong>and</strong> removal of the carbon brushes holder<br />

1. Disconnect the electric connection cables of the generator as described in<br />

section 4.8 on page 70.<br />

2. Unscrew the two screws M8 x 45, spanner size 10 mm, (Figure 31/2) <strong>and</strong><br />

detach the sleeve (1).<br />

3. Remove both connection cables from the connection lugs of the carbon<br />

brushes holder (Figure 31/5). The connection cables are coded by the width<br />

of the connection lugs <strong>and</strong> therefore secured against interchanging.<br />

4. Unscrew the fastening screw of the carbon brushes holder <strong>and</strong> detach the<br />

carbon brushes holder (Figure 31/5).<br />

5. Refer to the following descriptions to continue the removal:<br />

- For shaft fastening by grub-screw continue on page 95.<br />

- For shaft fastening by tension bolt continue on page 97.<br />

1 2<br />

3<br />

4<br />

5<br />

Figure 31<br />

Work prior to removal of single-bearing brush-type generators<br />

94 Issue date: August 2002