Chapter 2, Description<br />
2.8.2 Option insulation monitoring with switching-off<br />
If the generator is equipped with the option "Insulation monitoring with<br />
switching-off", it fulfills the protective measure "Protection separation with<br />
insulation monitoring" according to VDE 0100, part 728.<br />
The insulation monitoring unit (see Figure 6) monitors the insulation of the<br />
devices connected to the sockets. If it detects a defective insulation of a<br />
connected device or extension cord, the insulation monitoring unit immediately<br />
switches off all sockets <strong>and</strong> the red signal lamp "FAULTY INSULATION" lights up<br />
to indicate the fault. In this case the defective device has to be disconnected<br />
<strong>and</strong> taken out of operation <strong>and</strong> the insulation monitoring unit has to be reset.<br />
<strong>Generators</strong> which are equipped with an insulation monitoring unit<br />
must not be connected to further insulation monitoring units,<br />
since the insulation monitoring units can mutually interact.<br />
CAUTION<br />
24 Issue date: August 2002