<strong>Synchronous</strong> <strong>Generators</strong> <strong>BG</strong> <strong>132</strong> / <strong>BG</strong> <strong>160</strong><br />
Chapter 3, Technical data<br />
3 Technical data<br />
3.1 <strong>Generators</strong><br />
The technical data of the generator can be found on the type plate mounted on<br />
the generator.<br />
3.2 Control box (optional, only for 8 kVA <strong>and</strong> 13 kVA generators)<br />
Type of enclosure<br />
Connectors<br />
Features<br />
Optional features<br />
Permissible length of<br />
connected cables<br />
IP54 (all covers closed <strong>and</strong> locked)<br />
1 CEE socket 5 x 16 A (3P + N + PE)<br />
3 protective contact sockets 16 A (1P + N + PE)<br />
4-pole circuit breaker B 16 A<br />
Governor, filter <strong>and</strong> noise suppression installed<br />
Hour meter<br />
Insulation monitoring unit with signal lamp<br />
Fulfills protective measure "Protection separation<br />
with insulation monitoring" according to DVGW 308<br />
Total length of all connected cables:<br />
250 m max. at conductor cross section 2.5 mm 2<br />
100 m max. at conductor cross section 1.5 mm 2<br />
3.3 Generator governor<br />
Governor type<br />
LCAR3<br />
Pin assignment Pin Color Function<br />
1<br />
2<br />
3<br />
4<br />
5<br />
6<br />
red<br />
gray<br />
yellow<br />
yellow<br />
yellow<br />
F1<br />
F2<br />
1/2 U<br />
1/2 V<br />
1/2 W<br />
Issue date: August 2002 25