27.11.2014 Views

BaseStation 3200 User Manual – 11.7.5.15 ... - Baseline Systems

BaseStation 3200 User Manual – 11.7.5.15 ... - Baseline Systems

BaseStation 3200 User Manual – 11.7.5.15 ... - Baseline Systems

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

<strong>BaseStation</strong> <strong>3200</strong> Advanced Irrigation Controller <strong>Manual</strong><br />

the zone will be marked as good and watering will continue. If the variance is out of limit, then the zone<br />

will be marked as a failure and shut down. This method allows watering to continue almost without<br />

interruption, while isolating the faulty zone or zones.<br />

To set up the mainline<br />

1. Turn the dial to the Flow Menu position.<br />

2. Press the NEXT button to select Mainline Setup, and then press the ENTR button. The Mainline Setup screen<br />

displays.<br />

3. In the Mainline Number field, press the + or – button to select the number of the mainline that you want to<br />

set up.<br />

4. Press the NEXT button to go to the Design Flow GPM field, and then press the + button to enter the amount<br />

of flow in gallons per minute (GPM) that is allowed through the mainline for the irrigation system.<br />

Note: Press and hold the + button or the – button to rapidly increase or decrease the number in the field.<br />

5. Press the NEXT button to go to the Pipe Fill Time field, and then press the + button to enter the amount of<br />

time that it takes to fill the pipe and achieve a steady flow rate after a valve change.<br />

6. Press the NEXT button to go to the Limit by Flow field. If you want the controller to use the mainline design<br />

flow to determine how many zones can run concurrently, press the + button to enter Y (yes).<br />

7. Press the NEXT button to go to the High Alarm field. If you want to set an alarm for a high flow variance<br />

condition, press the + button to enter a percentage in the field.<br />

Example: If the expected flow is 50 GPM, and the High Alarm field is set to 10%, then the acceptable flow<br />

range is up to 55 GPM (10% of 50 GPM is 5 GPM). A flow amount over 55 GPM would trigger the high flow<br />

variance alarm.<br />

8. Press the NEXT button to go to the High Shutdown field. If you want<br />

the system to shut down when a high flow is detected, press the +<br />

button to enter Y (yes).<br />

9. Press the NEXT button to go to the Low Alarm field. If you want to set<br />

an alarm for a low flow variance condition, press the + button to enter<br />

a percentage in the field.<br />

Example: If the expected flow is 50 GPM, and the Low Alarm field is set<br />

to 10%, then the flow can decrease to 45 GPM (10% of 50 GPM is 5<br />

GPM). A flow amount below 45 GPM would trigger the low flow<br />

variance alarm.<br />

10. Press the NEXT button to go to the Low Shutdown field. If you want the system to shut down when a low flow<br />

is detected, press the + button to enter Y (yes).<br />

11. When you have finished making changes, turn the dial to the Auto Run position.<br />

Managing Concurrent Zones<br />

In the <strong>BaseStation</strong> <strong>3200</strong>, you manage the number of zones that can run concurrently at the following levels:<br />

• Mainline Flow Level – When you set up the design flow for the mainline and then set the Limit by Flow field to<br />

Y (yes), the system uses the mainline design flow to determine how many zones can run concurrently. Refer to<br />

Mainline Setup overview on page 59.<br />

• Controller and Program Level – If you want the controller to water more than one zone at a time, you must<br />

configure the Zone Concurrency settings at the controller and program level.<br />

Page 61

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!