Sheet DP020BREAKDOWN DETECTION FLOW CHARTTHE MOTOR DOES NOT STARTFROM THE TURNTABLE CONTROL PANEL BUT DOESSTART FROM THE PLATFORM CONTROL PANELFolio 1/1The motor does not start from the turntablecontrol panel but does start from theplatform control panel- Open the turntable control panel- Activate switch SB3 and check continuitybetween the two terminals of the switchSee FicheC044Replace the switch SB3NOContinuityOKENDYESActivate SB3 and check for12V voltage at terminal117A of the printed circuitRepair wiring of switch SB3(connection or replacement ofelectric wires)NO12VOKENDYESReplace the U1 moduleSee FicheC058 or C107NOThe faultpersistsENDYESReplace the printed circuitSee FicheC063END