MTL<strong>8000</strong> 2/x System specificationSystem specificationHAZARDOUS AREA APPROVALS - 2/2 NODE<strong>8000</strong> node equipment location*.......................Safe area or..............................................Zone 2, IIC T4 hazardous area or......................Class 1, Div 2, Groups A-D, T4 hazardous location*except for 8101-HI-TX, 8103-AI-TX and 8119-VI-05.............................................................................Safe area orZone 2, IIC T4 (T amb = 60°C), T3 (T amb = 70°C), hazardous area or............................Class 1, Div 2, Groups A-D, T4 (T amb = 60°C),..........................................T3 (T amb = 70°C) hazardous locationField equipment and wiring location.............................................................................Safe area or...................................................Zone 2, IIC hazardous area or...........................Class 1, Div 2, Groups A-D hazardous location(Temperature classification will be determined by the fieldapparatus)HAZARDOUS AREA APPROVALS - 2/1 NODE<strong>8000</strong> node equipment location ........................Safe area or..............................................Zone 2, IIC T4 hazardous area or......................Class 1, Div 2, Groups A-D, T4 hazardous locationField equipment and wiring location...................................................Zone 0, IIC hazardous area or...........................Class 1, Div 1, Groups A-D hazardous location(Temperature classification will be determined by the fieldapparatus)LOCAL AREA NETWORKFieldbus protocols supported.................Modbus (RTU mode).............................................................................Profibus - DPNote1. Protocols are selected by choice of Bus Interface Module2. For other protocols consult MTLConfiguration1) via host LAN (if supported by LAN)2) via PC connected locally at configuration portNode address setting ..................Software settable in the BIMLAN physical medium (configurable on carrier)...............LAN A.................................................RS485 or RS422, 5- wireLAN B (where available)........................RS485 or RS422, 5- wireLAN isolationLAN A to LAN B (if applicable).....................................250 V acLAN A or B to system ground .................250 V ac (to EN 61010)POWER SUPPLIESSystem SupplyLocal supply input........................................18.5 - 36 V dc inputSupply redundancy .................................................... supportedRailbus supply voltage...........................................12 V dc ± 5%Applicable standards:◆ Factory Mutual Research Co., Class No. 3611 for Class I,Division 2, Groups A, B, C, D hazardous locations◆ Factory Mutual Research Co., Class No. 3610 for Class I, II, III,Division 1, 2 Groups A-G hazardous locations◆ EN 50014: 1992 Electrical apparatus for potentially explosiveatmospheres, general requirements◆ EN 50020: 1995 Electrical apparatus for potentially explosiveatmospheres, intrinsically safe “i”◆ EN 50021: 1999 Electrical apparatus for potentially explosiveatmospheres, type of protection “n”◆ EC Directive 94/9/EC (ATEX 100A)IMPORTANTUsers are strongly recommended to refer to the System Specifier’s Guide (SSG8002) when designing a new systemEUROPE (EMEA) Tel: +44 (0)1582 723633 Fax: +44 (0)1582 422283AMERICAS Tel: +1 603 926 0090 Fax: +1 603 926 1899ASIA PACIFIC Tel: +65 487 7887 Fax: +65 487 7997E-mail: enquiry@mtl-inst.comWeb site: www.mtl-inst.comJune 2004
MTL<strong>8000</strong> 2/x System specification2/2 module cable parameters for non-incendive field wiringNoteFor module types 8109-DI-DC and 8122-DI-DC, each pair offield terminals may be considered as non-incendive whenconnected into a field circuit with the following parameters:V max = 30 V dc I max = 100 mA.The values of capacitance and inductance seen at themodule’s input terminals are:C i = 0 µF L i = 0 mH.ModuleFM(each channel) Gas Group C a (µF) L a (mH)8101-HI-TX A+B 0.17 11C 0.51 33D 1.36 888102-HO-IP A+B 0.17 11C 0.51 33D 1.36 888103-AI-TX A+B 0.17 11C 0.51 33D 1.36 888104-AO-IP A+B 0.17 11C 0.51 33D 1.36 888105-TI-TC A+B 14.9 1000C 44.8 1000D 119.6 10008106-TI-RT A+B 14.9 1000C 44.8 1000D 119.6 10008110-DI-DC A+B 0.12 151C 0.36 544D 0.97 10008119-VI-05 A+B 0.17 11C 0.51 33D 1.36 888121-DI-DC A+B 0.12 1000C 0.36 1000D 0.97 10008123-PI-QU A+B 1000 1000C 1000 1000D 1000 1000For the latest certification information visit : http://www.mtl-inst.com/certs_1.nsfEUROPE (EMEA) Tel: +44 (0)1582 723633 Fax: +44 (0)1582 422283AMERICAS Tel: +1 603 926 0090 Fax: +1 603 926 1899ASIA PACIFIC Tel: +65 487 7887 Fax: +65 487 7997E-mail: enquiry@mtl-inst.comWeb site: www.mtl-inst.comJune 2004