MTL<strong>8000</strong> 2/x System specification2/2 module cable parameters for non-incendive field wiringNoteFor module types 8109-DI-DC and 8122-DI-DC, each pair offield terminals may be considered as non-incendive whenconnected into a field circuit with the following parameters:V max = 30 V dc I max = 100 mA.The values of capacitance and inductance seen at themodule’s input terminals are:C i = 0 µF L i = 0 mH.ModuleFM(each channel) Gas Group C a (µF) L a (mH)8101-HI-TX A+B 0.17 11C 0.51 33D 1.36 888102-HO-IP A+B 0.17 11C 0.51 33D 1.36 888103-AI-TX A+B 0.17 11C 0.51 33D 1.36 888104-AO-IP A+B 0.17 11C 0.51 33D 1.36 888105-TI-TC A+B 14.9 1000C 44.8 1000D 119.6 10008106-TI-RT A+B 14.9 1000C 44.8 1000D 119.6 10008110-DI-DC A+B 0.12 151C 0.36 544D 0.97 10008119-VI-05 A+B 0.17 11C 0.51 33D 1.36 888121-DI-DC A+B 0.12 1000C 0.36 1000D 0.97 10008123-PI-QU A+B 1000 1000C 1000 1000D 1000 1000For the latest certification information visit : http://www.mtl-inst.com/certs_1.nsfEUROPE (EMEA) Tel: +44 (0)1582 723633 Fax: +44 (0)1582 422283AMERICAS Tel: +1 603 926 0090 Fax: +1 603 926 1899ASIA PACIFIC Tel: +65 487 7887 Fax: +65 487 7997E-mail: enquiry@mtl-inst.comWeb site: www.mtl-inst.comJune 2004