MTL<strong>8000</strong> 2/x System specification2/1 module cable parameters for IS field wiringModule BASEEFA FM(each channel) Gas Group µF mH or µH/Ω Gas Group C a (µF) L a (mH)8201-HI-IS IIC 0.083 4.3 56 A+B 0.14 4.38IIB 0.65 17.72 210 C 0.43 17.2IIA 2.15 36.02 444 D 1.14 34.28202-HO-IS IIC 0.116 4.3 64 - - -IIB 0.87 17.7 239 - - -IIA 3.12 36 505 - - -8204-AO-IS IIC 0.136 4.80 71 A+B 0.21 4.67IIB 1.00 19.61 265 C 0.64 18.3IIA 3.60 40.04 558 D 1.70 36.58205-TI-ISChannels 1, 2, 3, 4, 7 and 8 wired as separate IS circuitIIC 0.41 5.8 62 A+B 0.41 8.5IIB 2.49 23.8 227 C 2.44 32.4IIA 9.98 49.1 480 D 9.98 69.2Channels 5 and 6 wired as separate IS circuitIIC 100 1000 1100 A+B 1000 1000IIB 100 1000 1100 C 1000 1000IIA 100 1000 1100 D 1000 10008206-TI-IS IIC 0.389 0.39 20 A+B 0.39 0.3IIB 2.47 1.5 90 C 2.47 1.3IIA 9.96 4.2 182 D 9.96 2.428215-DO-IS IIC 0.11 3.08 53 A+B 0.19 3.15IIB 0.84 13.02 205 C 0.56 12.5IIA 2.97 26.12 432 D 1.51 24.58220-DI-IS IIC 2.41 175 983 A+B 2.67 176IIB 16.80 680 1333 C 8.00 633IIA 75.00 1000 1333 D 21.3 10008223-PI-IS IIC 0.078 1.28 15 A+B 1000 10.6IIB 0.627 3.86 56 C 1000 40.4IIA 2.05 10.29 119 D 1000 87.18230-AI-IS IIC 0.47 87.5 334 - - --IIB 2.88 328 952 - - --IIA 11.6 633 952 - - -For the latest certification information visit: http://www.mtl-inst.com/certs_1.nsfEUROPE (EMEA) Tel: +44 (0)1582 723633 Fax: +44 (0)1582 422283AMERICAS Tel: +1 603 926 0090 Fax: +1 603 926 1899ASIA PACIFIC Tel: +65 487 7887 Fax: +65 487 7997E-mail: enquiry@mtl-inst.comWeb site: www.mtl-inst.comJune 2004