LEGEND NOTES:<br />

1. Remote device.<br />

2. Transformer connected for 480 v primary 120 v secondary. For other<br />

voltages see chart:<br />

PRIMARY SECONDARY<br />

H1-H2 H1-H3 H1-H4 H1-H5 X1-X2 X1-X3 X1-X4<br />

240 416 480 600 99 120 130<br />

230 400 460 575 95 115 125<br />

LL — Control Power Supply<br />

M — Contactor<br />

OP — Oil Pump<br />

PFCC — Power Factor Correction Capacitor<br />

RES — Resistor<br />

S — Contactor<br />

ST — Shunt Trip<br />

TB — Terminal Block<br />

TC — Transition Contactor<br />

VL — Wire Label<br />

C — Contactor<br />

CB — Circuit Breaker<br />

CP — Control Power<br />

CT — Current Transformer<br />

DS — Disconnect Switch<br />

FU — Fuse<br />

GRD — Ground<br />

HPR — High Pressure Relay<br />

ISM — Integrated <strong>Start</strong>er Module<br />

L — Main Supply Power<br />

220 380 440 550 91 110 120<br />

208 500 85 100 110<br />

3. Current transformer<br />

•amps nameplate ratio<br />

•amps effective ratio with primary turns<br />

•polarity marking<br />

Be sure to connect per polarity markings.<br />

4. “S” - “2M” contactors are electrically <strong>and</strong> mechanically interlocked.<br />

5. Live capacitor unit. Deenergize starter. Wait one (1) minute <strong>and</strong> ground<br />

terminals before servicing.<br />

6. All control wiring 14 gage red except as noted.<br />

Fig. 45 — Allen-Bradley Wye-Delta Unit-Mounted <strong>Start</strong>er (cont)