Table 2 — CVC/ICVC Display Data (cont)<br />

EXAMPLE 21 — RAMP_DEM DISPLAY SCREEN<br />

To access this display from the CVC/ICVC default screen:<br />

1. Press MENU .<br />

2. Press SERVICE .<br />

3. Scroll down to highlight EQUIPMENT SERVICE .<br />

4. Press SELECT .<br />

5. Scroll down to highlight RAMP_DEM .<br />

6. Press SELECT .<br />

DESCRIPTION STATUS UNITS POINT DEFAULT<br />

Pulldown Ramp Type: 0/1 ramp_opt 1<br />

Select: Temp=0, Load=1<br />

Dem<strong>and</strong> Limit + kW Ramp<br />

Dem<strong>and</strong> Limit Source 0/1 dem_src 0<br />

Select: Amps=0, kW=1<br />

Motor Load Ramp% Min 5-20 kw_ramp 10<br />

Dem<strong>and</strong> Limit Prop B<strong>and</strong> 3-15 % dem_prop 10<br />

Dem<strong>and</strong> Limit At 20 mA 40-100 % dem_20ma 40<br />

20 mA Dem<strong>and</strong> Limit Opt 0/1 DSABLE/ENABLE dem_sel DSABLE<br />

Motor Rated Kilowatts 50-9999 kW motor_kw 145<br />

Dem<strong>and</strong> Watts Interval 5-60 MIN dw_int 15<br />

NOTE: No variables are available for CCN read or write operation.<br />

EXAMPLE 22 — TEMP_CTL DISPLAY SCREEN<br />

To access this display from the CVC/ICVC default screen:<br />

1. Press MENU .<br />

2. Press SERVICE .<br />

3. Scroll down to highlight EQUIPMENT SERVICE .<br />

4. Press SELECT .<br />

5. Scroll down to highlight TEMP_CTL .<br />

6. Press SELECT<br />

.<br />

DESCRIPTION<br />

Control Point<br />

STATUS UNITS POINT DEFAULT<br />

ECW Control Option 0/1 DSABLE/ENABLE ecw_opt DSABLE<br />

Temp Pulldown Deg/Min<br />

Temperature Reset<br />

RESET TYPE 1<br />

2-10 ^F temp_ramp 3<br />

Degrees Reset At 20 mA<br />

RESET TYPE 2<br />

–30- 30 ^F deg_20ma 10<br />

Remote Temp —> No Reset –40-245 DEG F res_rt1 85<br />

Remote Temp —> Full Reset –40-245 DEG F res_rt2 65<br />

Degrees Reset<br />

RESET TYPE 3<br />

–30-30 ^F deg_rt 10<br />

CHW Delta T —> No Reset 0-15 ^F restd_1 10<br />

CHW Delta T —> Full Reset 0-15 ^F restd_2 0<br />

Degrees Reset –30-30 ^F deg_chw 5<br />

Select/Enable Reset Type 0-3 res_sel 0<br />