Table 2 — CVC/ICVC Display Data (cont)<br />
EXAMPLE 21 — RAMP_DEM DISPLAY SCREEN<br />
To access this display from the CVC/ICVC default screen:<br />
1. Press MENU .<br />
2. Press SERVICE .<br />
3. Scroll down to highlight EQUIPMENT SERVICE .<br />
4. Press SELECT .<br />
5. Scroll down to highlight RAMP_DEM .<br />
6. Press SELECT .<br />
DESCRIPTION STATUS UNITS POINT DEFAULT<br />
Pulldown Ramp Type: 0/1 ramp_opt 1<br />
Select: Temp=0, Load=1<br />
Dem<strong>and</strong> Limit + kW Ramp<br />
Dem<strong>and</strong> Limit Source 0/1 dem_src 0<br />
Select: Amps=0, kW=1<br />
Motor Load Ramp% Min 5-20 kw_ramp 10<br />
Dem<strong>and</strong> Limit Prop B<strong>and</strong> 3-15 % dem_prop 10<br />
Dem<strong>and</strong> Limit At 20 mA 40-100 % dem_20ma 40<br />
20 mA Dem<strong>and</strong> Limit Opt 0/1 DSABLE/ENABLE dem_sel DSABLE<br />
Motor Rated Kilowatts 50-9999 kW motor_kw 145<br />
Dem<strong>and</strong> Watts Interval 5-60 MIN dw_int 15<br />
NOTE: No variables are available for CCN read or write operation.<br />
EXAMPLE 22 — TEMP_CTL DISPLAY SCREEN<br />
To access this display from the CVC/ICVC default screen:<br />
1. Press MENU .<br />
2. Press SERVICE .<br />
3. Scroll down to highlight EQUIPMENT SERVICE .<br />
4. Press SELECT .<br />
5. Scroll down to highlight TEMP_CTL .<br />
6. Press SELECT<br />
.<br />
DESCRIPTION<br />
Control Point<br />
STATUS UNITS POINT DEFAULT<br />
ECW Control Option 0/1 DSABLE/ENABLE ecw_opt DSABLE<br />
Temp Pulldown Deg/Min<br />
Temperature Reset<br />
RESET TYPE 1<br />
2-10 ^F temp_ramp 3<br />
Degrees Reset At 20 mA<br />
RESET TYPE 2<br />
–30- 30 ^F deg_20ma 10<br />
Remote Temp —> No Reset –40-245 DEG F res_rt1 85<br />
Remote Temp —> Full Reset –40-245 DEG F res_rt2 65<br />
Degrees Reset<br />
RESET TYPE 3<br />
–30-30 ^F deg_rt 10<br />
CHW Delta T —> No Reset 0-15 ^F restd_1 10<br />
CHW Delta T —> Full Reset 0-15 ^F restd_2 0<br />
Degrees Reset –30-30 ^F deg_chw 5<br />
Select/Enable Reset Type 0-3 res_sel 0<br />
32