Table 2 — CVC/ICVC Display Data (cont)<br />

EXAMPLE 19 — SETUP2 DISPLAY SCREEN<br />

To access this display from the CVC/ICVC default screen:<br />

1. Press MENU .<br />

2. Press SERVICE .<br />

3. Scroll down to highlight EQUIPMENT SERVICE .<br />

4. Press SELECT .<br />

5. Scroll down to highlight SETUP2 .<br />

6. Press SELECT .<br />

DESCRIPTION<br />

Capacity Control<br />

STATUS UNITS POINT DEFAULT<br />

Proportional Inc B<strong>and</strong> 2-10 gv_inc 6.5<br />

Proportional DEC B<strong>and</strong> 2-10 gv_dec 6.0<br />

Proportional ECW B<strong>and</strong> 1-3 gw_ecw 2<br />

Guide Vane Travel Limit<br />

Diffuser Control<br />

30-100 % gv_lim 80<br />

Diffuser Option 0-1 DSABLE/ENABLE diff_opt DSABLE<br />

Guide Vane 25% Load Pt 0-78 % gv_25 25<br />

Diffuser 25% Load Point 0-100 % df_25 0<br />

Guide Vane 50% Load Pt 0-78 % gv_50 50<br />

Diffuser 50% Load Point 0-100 % df_50 0<br />

Guide Vane 75% Load Pt 0-78 % gv_75 75<br />

Diffuser 75% Load Point 0-100 % df_75 0<br />

Diffuser Full Span mA<br />

VFD Speed Control<br />

15-22 mA diff_ma 18<br />

VFD Option 0/1 DSABLE/ENABLE vfd_opt DSABLE<br />

VFD Gain 0.1-1.5 vfd_gain 0.75<br />

VFD Increase Step 1-5 % vfd_step 2<br />

VFD Minimum Speed 65-100 % vfd_min 70<br />

VFD Maximum Speed 90-100 % vfd_max 100<br />

VFD Current Limit 0-99999 Amps vfdlim_i 250<br />

NOTE: No variables are available for CCN read or write operation; forcing shall not be supported on service screens.<br />

EXAMPLE 20 — LEADLAG DISPLAY SCREEN<br />

To access this display from the CVC/ICVC default screen:<br />

1. Press MENU .<br />

2. Press SERVICE .<br />

3. Scroll down to highlight EQUIPMENT SERVICE .<br />

4. Press SELECT .<br />

5. Scroll down to highlight LEADLAG .<br />

6. Press SELECT<br />

.<br />

DESCRIPTION STATUS UNITS POINT DEFAULT<br />

Lead Lag Control<br />

LEAD/LAG: Configuration 0-3 leadlag 0<br />

DSABLE=0, Lead=1<br />

LAG=2, STANDBY=3<br />

Load Balance Option 0/1 DSABLE/ENABLE load/bal DSABLE<br />

Common Sensor Option 0/1 DSABLE/ENABLE commsens DSABLE<br />

LAG % Capacity 25-75 % lag_per 50<br />

LAG Address 1-236 lag_add 92<br />

LAG START Timer 2-60 MIN lagstart 10<br />

LAG STOP Timer 2-60 MIN lagstop 10<br />

PRESTART FAULT Timer 2-30 MIN preft 5<br />

STANDBY Chiller Option 0/1 DSABLE/ENABLE stndopt DSABLE<br />

STANDBY % Capacity 25-75 % stnd_per 50<br />

STANDBY Address 1-236 stnd_add 93<br />

NOTE: No variables are available for CCN read or write operation.<br />

31