I. CHILLER PROTECT LIMIT FAULTS<br />

STATE<br />

PRIMARY<br />

MESSAGE<br />

200 PROTECTIVE<br />

LIMIT<br />

201 PROTECTIVE<br />

LIMIT<br />

202 PROTECTIVE<br />

LIMIT<br />

203 FAILURE TO<br />

START<br />

204 FAILURE TO<br />

STOP<br />

205 FAILURE TO<br />

STOP<br />

206 PROTECTIVE<br />

LIMIT<br />

207 PROTECTIVE<br />

LIMIT<br />

208 PROTECTIVE<br />

LIMIT<br />

209 PROTECTIVE<br />

LIMIT<br />

210 PROTECTIVE<br />

LIMIT<br />

211 PROTECTIVE<br />

LIMIT<br />

212 PROTECTIVE<br />

LIMIT<br />

213 PROTECTIVE<br />

LIMIT<br />

214 PROTECTIVE<br />

LIMIT<br />

215 PROTECTIVE<br />

LIMIT<br />

216 PROTECTIVE<br />

LIMIT<br />

217 PROTECTIVE<br />

LIMIT<br />

218 PROTECTIVE<br />

LIMIT<br />

219 PROTECTIVE<br />

LIMIT<br />

220 PROTECTIVE<br />

LIMIT<br />

221 PROTECTIVE<br />

LIMIT<br />

222 PROTECTIVE<br />

LIMIT<br />

223 PROTECTIVE<br />

LIMIT<br />

Table 11 — CVC/ICVC Primary <strong>and</strong> Secondary Messages <strong>and</strong><br />

Custom Alarm/Alert Messages with Troubleshooting Guides (cont)<br />

SECONDARY<br />

MESSAGE<br />

1M CONTACT<br />

FAULT<br />

2M CONTACT<br />

FAULT<br />

MOTOR AMPS<br />

NOT SENSED<br />

EXCESS<br />

ACCELERATION<br />

TIME<br />

1M/2M CONTACT<br />

FAULT<br />

MOTOR AMPS<br />

WHEN STOPPED<br />

STARTER<br />

FAULT<br />

HIGH CONDENSER<br />

PRESSURE<br />

EXCESSIVE<br />

MOTOR AMPS<br />

LINE PHASE<br />

LOSS<br />

LINE VOLTAGE<br />

DROPOUT<br />

HIGH LINE<br />

VOLTAGE<br />

LOW LINE<br />

VOLTAGE<br />

ALARM MESSAGE<br />

PRIMARY CAUSE<br />

200->1M Aux Contact Fault;<br />

Check 1M Contactor <strong>and</strong><br />

Aux<br />

201->2M Aux Contact Fault;<br />

Check 2M Contactor <strong>and</strong><br />

Aux<br />

202->Motor Amps Not<br />

Sensed — Average Line<br />

Current [VALUE]<br />

203->Motor Acceleration<br />

Fault — Average Line<br />

Current [VALUE]<br />

204->1M/2M Aux Contact<br />

Stop Fault; Check 1M/2M<br />

Contactors <strong>and</strong> Aux<br />

205->Motor Amps When<br />

Stopped — Average Line<br />

Current [VALUE]<br />

206-><strong>Start</strong>er Fault Cutout;<br />

Check Optional <strong>Start</strong>er<br />

Contacts<br />

207->High Cond Pressure<br />

cutout. [VALUE] exceeded<br />

limit of [LIMIT]*.<br />

208->Compressor Motor<br />

Amps [VALUE] exceeded<br />

limit of [LIMIT]*.<br />

209->Line Phase Loss;<br />

Check ISM Fault History to<br />

Identify Phase<br />

210->Single Cycle Line<br />

Voltage Dropout<br />

211->High Average Line<br />

Voltage [VALUE]<br />

212->Low Average Line<br />

Voltage [VALUE]<br />

STARTER MODULE 213-><strong>Start</strong>er Module Power-<br />

RESET<br />

On Reset When Running<br />

POWER LOSS 214->Power Loss:<br />

Check voltage supply<br />

LINE CURRENT<br />

IMBALANCE<br />

LINE VOLTAGE<br />

IMBALANCE<br />

MOTOR OVERLOAD<br />

TRIP<br />

MOTOR LOCKED<br />

ROTOR TRIP<br />

215->Line Current<br />

Imbalance; Check ISM Fault<br />

History to Identify Phase<br />

216->Line Voltage<br />

Imbalance; Check ISM Fault<br />

History to Identify Phase<br />

217->Motor Overload Trip;<br />

Check ISM configurations<br />

218->Motor Locked Rotor<br />

Amps exceeded; Check<br />

Motor & ISM Config<br />

219-><strong>Start</strong>er Locked Rotor<br />

Amps Rating exceeded<br />

STARTER LOCK<br />

ROTOR TRIP<br />

GROUND FAULT 220->Ground Fault Trip;<br />

Check Motor <strong>and</strong> Current<br />

Transformers<br />

PHASE REVERSAL 221->Phase Reversal Trip;<br />

TRIP<br />

Check Power Supply<br />

LINE FREQUENCY 222->Line Frequency —<br />

TRIP<br />

[VALUE] exceeded limit of<br />

[LIMIT]. Check Power<br />

Supply.<br />

STARTER MODULE 223-><strong>Start</strong>er Module<br />

FAILURE<br />

Hardware Failure<br />

81<br />

ADDITIONAL<br />

CAUSE/REMEDY<br />

Check for wiring of current transformers to the ISM.<br />

Check main circuit breaker for trip.<br />

Check to be sure that the inlet guide vanes are closed<br />

at start-up.<br />

Check starter for proper operation.<br />

Reduce unit pressure if possible.<br />

For Benshaw Inc. Redi<strong>Start</strong> MICRO starters, view<br />

fault code at Redi<strong>Start</strong> MICRO display. Press FAULT<br />

RESET to clear faults.<br />

Check for high condenser water temperatures, low<br />

water flow, fouled tubes.<br />

Check for division plate/gasket bypass.<br />

Check for noncondensables.<br />

Check transducer wiring <strong>and</strong> accuracy.<br />

If [VALUE] is less than Limit then check the<br />

1CR <strong>Start</strong>ing Circuit.<br />

Check motor current for proper calibration.<br />

Check inlet guide vane actuator.<br />

Check transformers to ISM.<br />

Check power distribution bus.<br />

Consult power company.<br />

Check transformers to ISM.<br />

Check distribution bus.<br />

Consult power company.<br />

Check transformers to ISM.<br />

Check distribution bus.<br />

Consult power company.<br />

Check transformers to ISM.<br />

Check distribution bus.<br />

Consult power company.<br />

Check upstream equipment.<br />

Check upstream equipment.<br />

Check ISM configuration.<br />

Check ISM configuration.<br />

Check ISM configuration.