Table 2 — CVC/ICVC Display Data (cont)<br />

EXAMPLE 17 — OPTIONS DISPLAY SCREEN<br />

To access this display from the CVC/ICVC default screen:<br />

1. Press MENU .<br />

2. Press SERVICE .<br />

3. Scroll down to highlight EQUIPMENT SERVICE .<br />

4. Press SELECT .<br />

5. Scroll down to highlight OPTIONS .<br />

6. Press SELECT .<br />

DESCRIPTION STATUS UNITS POINT DEFAULT<br />

Auto Restart Option 0/1 DSABLE/ENABLE start DSABLE<br />

Remote Contacts Option 0/1 DSABLE/ENABLE r_contact DSABLE<br />

Soft Stop Amps Threshold 40-100 % softstop 100<br />

Surge / Hot Gas Bypass<br />

Surge Limit/HGBP Option 0/1 srg_hgbp 0<br />

Select: Surge=0, HGBP=1<br />

Min. Load Point (T1,P1)<br />

Surge/HGBP Delta T1 0.5-20 ^F hgb_dt1 1.5<br />

Surge/HGBP Delta P1 30-170 PSI hgb_dp1 50<br />

Full Load Point (T2,P2)<br />

Surge/HGBP Delta T2 0.5-20 ^F hbg_dt2 10<br />

Surge/HGBP Delta P2 50-170 PSI hgb_dp2 85<br />

Surge/HGBP Deadb<strong>and</strong> 0.5-3 ^F hbg_db 1<br />

Surge Protection<br />

Surge Delta% Amps 5-20 % surge_a 10<br />

Surge Time Period 7-10 MIN surge_t 8<br />

Ice Build Control<br />

Ice Build Option 0/1 DSABLE/ENABLE ibopt DSABLE<br />

Ice Build Termination 0-2 ibterm 0<br />

0=Temp, 1=Contacts, 2=Both<br />

Ice Build Recycle 0/1 DSABLE/ENABLE ibrecyc DSABLE<br />

Refrigerant Leak Option 0/1 DSABLE/ENABLE DSABLE<br />

Refrigerant Leak Alarm mA 4-20 mA REF_LEAK 20<br />

Head Pressure Reference<br />

Delta P at 0% (4mA) 20-60 PSI HPDPO 25<br />

Delta P at 100% (20mA) 20-60 PSI HPDP100 35<br />

Minimum Output 0-100 % HPDPMIN% 0<br />

NOTE: No variables are available for CCN read or write operation.<br />

EXAMPLE 18 — SETUP1 DISPLAY SCREEN<br />

To access this display from the CVC/ICVC default screen:<br />

1. Press MENU .<br />

2. Press SERVICE .<br />

3. Scroll down to highlight EQUIPMENT SERVICE .<br />

4. Press SELECT .<br />

5. Scroll down to highlight SETUP1 .<br />

6. Press SELECT<br />

.<br />

DESCRIPTION STATUS UNITS POINT DEFAULT<br />

Comp Motor Temp Override 150-200 DEG F mt_over 200<br />

Cond Press Override 90-165 PSI cp_over 125<br />

Comp Discharge Alert 125-200 DEG F cd_alert 200<br />

Comp Thrust Brg Alert 165-185 DEG F tb_alert 175<br />

Chilled Medium 0/1 WATER/BRINE medium WATER<br />

Chilled Water Deadb<strong>and</strong> .5-2.0 ^F cw _db 1.0<br />

Evap Refrig Trippoint 0.0-40.0 DEG F ert_trip 33<br />

Refrig Override Delta T 2.0-5.0 ^F ref_over 3<br />

Condenser Freeze Point –20 - 35 DEG F cdfreeze 34<br />

Evap Flow Delta P Cutout 0.5 - 50.0 PSI evap_cut 5.0<br />

Cond Flow Delta P Cutout 0.5 - 50.0 PSI cond_cut 5.0<br />

Water Flow Verify Time 0.5-5 MIN wflow_t 5<br />

Oil Pressure Verify Time<br />

Recycle Control<br />

15-300 SEC oilpr_t 40<br />

Restart Delta T 2.0-10.0 DEG F rcycr_dt 5<br />

Shutdown Delta T<br />

SPARE ALERT/ALARM ENABLE<br />

Disable=0, Lo=1/3, Hi=2/4<br />

0.5-4.0 DEG F rcycs_dt 1<br />

Spare Temp #1 Enable 0-4 sp1_en 0<br />

Spare Temp #1 Limit –40-245 DEG F sp1_lim 245<br />

Spare Temp #2 Enable 0-4 sp2_ en 0<br />

Spare Temp #2 Limit –40-245 DEG F sp2_ lim 245<br />

NOTE: No variables are available for CCN read or write operation; forcing shall not be supported on service screens.<br />