Table 2 — CVC/ICVC Display Data (cont)<br />
EXAMPLE 17 — OPTIONS DISPLAY SCREEN<br />
To access this display from the CVC/ICVC default screen:<br />
1. Press MENU .<br />
2. Press SERVICE .<br />
3. Scroll down to highlight EQUIPMENT SERVICE .<br />
4. Press SELECT .<br />
5. Scroll down to highlight OPTIONS .<br />
6. Press SELECT .<br />
DESCRIPTION STATUS UNITS POINT DEFAULT<br />
Auto Restart Option 0/1 DSABLE/ENABLE start DSABLE<br />
Remote Contacts Option 0/1 DSABLE/ENABLE r_contact DSABLE<br />
Soft Stop Amps Threshold 40-100 % softstop 100<br />
Surge / Hot Gas Bypass<br />
Surge Limit/HGBP Option 0/1 srg_hgbp 0<br />
Select: Surge=0, HGBP=1<br />
Min. Load Point (T1,P1)<br />
Surge/HGBP Delta T1 0.5-20 ^F hgb_dt1 1.5<br />
Surge/HGBP Delta P1 30-170 PSI hgb_dp1 50<br />
Full Load Point (T2,P2)<br />
Surge/HGBP Delta T2 0.5-20 ^F hbg_dt2 10<br />
Surge/HGBP Delta P2 50-170 PSI hgb_dp2 85<br />
Surge/HGBP Deadb<strong>and</strong> 0.5-3 ^F hbg_db 1<br />
Surge Protection<br />
Surge Delta% Amps 5-20 % surge_a 10<br />
Surge Time Period 7-10 MIN surge_t 8<br />
Ice Build Control<br />
Ice Build Option 0/1 DSABLE/ENABLE ibopt DSABLE<br />
Ice Build Termination 0-2 ibterm 0<br />
0=Temp, 1=Contacts, 2=Both<br />
Ice Build Recycle 0/1 DSABLE/ENABLE ibrecyc DSABLE<br />
Refrigerant Leak Option 0/1 DSABLE/ENABLE DSABLE<br />
Refrigerant Leak Alarm mA 4-20 mA REF_LEAK 20<br />
Head Pressure Reference<br />
Delta P at 0% (4mA) 20-60 PSI HPDPO 25<br />
Delta P at 100% (20mA) 20-60 PSI HPDP100 35<br />
Minimum Output 0-100 % HPDPMIN% 0<br />
NOTE: No variables are available for CCN read or write operation.<br />
EXAMPLE 18 — SETUP1 DISPLAY SCREEN<br />
To access this display from the CVC/ICVC default screen:<br />
1. Press MENU .<br />
2. Press SERVICE .<br />
3. Scroll down to highlight EQUIPMENT SERVICE .<br />
4. Press SELECT .<br />
5. Scroll down to highlight SETUP1 .<br />
6. Press SELECT<br />
.<br />
DESCRIPTION STATUS UNITS POINT DEFAULT<br />
Comp Motor Temp Override 150-200 DEG F mt_over 200<br />
Cond Press Override 90-165 PSI cp_over 125<br />
Comp Discharge Alert 125-200 DEG F cd_alert 200<br />
Comp Thrust Brg Alert 165-185 DEG F tb_alert 175<br />
Chilled Medium 0/1 WATER/BRINE medium WATER<br />
Chilled Water Deadb<strong>and</strong> .5-2.0 ^F cw _db 1.0<br />
Evap Refrig Trippoint 0.0-40.0 DEG F ert_trip 33<br />
Refrig Override Delta T 2.0-5.0 ^F ref_over 3<br />
Condenser Freeze Point –20 - 35 DEG F cdfreeze 34<br />
Evap Flow Delta P Cutout 0.5 - 50.0 PSI evap_cut 5.0<br />
Cond Flow Delta P Cutout 0.5 - 50.0 PSI cond_cut 5.0<br />
Water Flow Verify Time 0.5-5 MIN wflow_t 5<br />
Oil Pressure Verify Time<br />
Recycle Control<br />
15-300 SEC oilpr_t 40<br />
Restart Delta T 2.0-10.0 DEG F rcycr_dt 5<br />
Shutdown Delta T<br />
SPARE ALERT/ALARM ENABLE<br />
Disable=0, Lo=1/3, Hi=2/4<br />
0.5-4.0 DEG F rcycs_dt 1<br />
Spare Temp #1 Enable 0-4 sp1_en 0<br />
Spare Temp #1 Limit –40-245 DEG F sp1_lim 245<br />
Spare Temp #2 Enable 0-4 sp2_ en 0<br />
Spare Temp #2 Limit –40-245 DEG F sp2_ lim 245<br />
NOTE: No variables are available for CCN read or write operation; forcing shall not be supported on service screens.<br />
30