- Page 1 and 2:
Start-Up, Operation, and Maintenanc
- Page 3 and 4:
CONTENTS (cont) Page Page Chiller D
- Page 5 and 6:
Factory-installed additional compon
- Page 7 and 8:
Factory-Mounted Starter or Variable
- Page 9 and 10:
MOTOR COOLING LINE TXV BULB PRESSUR
- Page 11 and 12:
OPTIONAL METER PACKAGE INTEGRATED S
- Page 13 and 14:
The PIC II can interface with the C
- Page 15 and 16:
CVC/ICVC Operation and Menus (Fig.
- Page 17 and 18:
Start Chiller In CCN Control Start
- Page 19 and 20:
SERVICE MENU CONTINUED FROM PREVIOU
- Page 21 and 22:
7. Press ENTER to register the valu
- Page 23 and 24:
Table 2 — CVC/ICVC Display Data (
- Page 25 and 26:
Table 2 — CVC/ICVC Display Data (
- Page 27 and 28:
Table 2 — CVC/ICVC Display Data (
- Page 29 and 30:
Table 2 — CVC/ICVC Display Data (
- Page 31 and 32:
Table 2 — CVC/ICVC Display Data (
- Page 33 and 34:
PIC II System Functions NOTE: Words
- Page 35 and 36:
Shunt Trip (Option) — The functio
- Page 37 and 38:
OVERRIDE CAPACITY CONTROL HIGH COND
- Page 39 and 40:
(see wiring diagrams or certified d
- Page 41 and 42:
NOTE: The lead/lag function can be
- Page 43 and 44:
Ice Build Control — The ice build
- Page 45 and 46:
Service Operation — An overview o
- Page 47 and 48:
Shutdown Sequence — Chiller shutd
- Page 49 and 50:
49 Fig. 28 — 19XR Leak Test Proce
- Page 51 and 52:
Fig. 29 — Typical Optional Pumpou
- Page 53 and 54:
Chiller Dehydration — Dehydration
- Page 55 and 56:
MECHANICAL STARTER 1. Check all fie
- Page 57 and 58:
CHANGE THE BENSHAW INC., RediStart
- Page 59 and 60:
VFD Cooling System Leak Inspection
- Page 61 and 62:
Protecting the VFD Configuration 1.
- Page 63 and 64:
Check Optional Pumpout System Contr
- Page 65 and 66:
Dry Run to Test Start-Up Sequence F
- Page 67 and 68: Leave the oil charge in the chiller
- Page 69 and 70: LEGEND C — Contactor FU — Fuse,
- Page 71 and 72: 2. Evacuate the refrigerant gas fro
- Page 73 and 74: SCHEDULED MAINTENANCE Establish a r
- Page 75 and 76: Water Treatment — Untreated or im
- Page 77 and 78: TRANSDUCER REPLACEMENT — Since th
- Page 79 and 80: Table 11 — CVC/ICVC Primary and S
- Page 81 and 82: I. CHILLER PROTECT LIMIT FAULTS STA
- Page 83 and 84: I. CHILLER PROTECT LIMIT FAULTS (co
- Page 85 and 86: TEMPERATURE (F) PIC II VOLTAGE DROP
- Page 87 and 88: Control Modules Turn controller pow
- Page 89 and 90: ANALOG OUT J8 INTERGRATED STARTER M
- Page 91 and 92: NOTES: 1. Cooler data: based on a c
- Page 93 and 94: Table 14 — 19XR Additional Data f
- Page 95 and 96: HEAT EXCHANGER COOLER/ CONDENSER HE
- Page 97 and 98: Table 18 — Optional Pumpout Syste
- Page 99 and 100: ITEM A B C D E F VIEW B — HIGH SP
- Page 101 and 102: 101 Fig. 45 — Allen-Bradley Wye-D
- Page 103 and 104: 103 LEGEND (cont) ISM — Integrate
- Page 105 and 106: 105 LEGEND (cont) ISM — Integrate
- Page 107 and 108: 107 LEGEND Denotes Component Termin
- Page 109 and 110: AUX — Auxiliary C — Contactor C
- Page 111 and 112: Fig. 53 — Benshaw, Inc. Solid-Sta
- Page 113 and 114: LEGEND AUX — Auxiliary C — Cont
- Page 115 and 116: 1A LEGEND AUX — Auxiliary C — C
- Page 117: 117 Fig. 57 — Typical Variable Fr
- Page 121 and 122: 121 Fig. 57 — Typical Variable Fr
- Page 123 and 124: Abbreviations and Explanations, 4 A
- Page 125 and 126: MACHINE INFORMATION: DESIGN CONDITI
- Page 127 and 128: 19XR, XRV PIC II SETPOINT TABLE CON
- Page 129 and 130: CUT ALONG DOTTED LINE CUT ALONG DOT
- Page 131 and 132: CUT ALONG DOTTED LINE CUT ALONG DOT
- Page 133 and 134: CUT ALONG DOTTED LINE CUT ALONG DOT
- Page 135 and 136: CUT ALONG DOTTED LINE CUT ALONG DOT
- Page 137 and 138: CUT ALONG DOTTED LINE CUT ALONG DOT
- Page 140: Copyright 2001 Carrier Corporation