10.04.2013 Views

Start-Up, Operation, and Maintenance Instructions

Start-Up, Operation, and Maintenance Instructions

Start-Up, Operation, and Maintenance Instructions

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

LEGEND<br />

C — Contactor<br />

FU — Fuse, 3 Amps<br />

HP — High-Pressure Cutout<br />

OL — Compressor Overload<br />

T’STAT — Internal Thermostat<br />

Compressor Terminal<br />

Contactor Terminal<br />

Overload Terminal<br />

Pumpout Unit Terminal<br />

*Bimetal thermal protector imbedded in motor winding.<br />

Fig. 35 — 19XR Pumpout Unit Wiring Schematic<br />

OIL RETURN<br />

LINE<br />

CONNECTION<br />

CONDENSER<br />

WATER<br />

CONNECTIONS<br />

REFRIGERANT<br />

INLET VALVE<br />

Fig. 36 — Optional Pumpout Unit<br />

Chillers with Storage Tanks — If the chiller has isolation<br />

valves, leave them open for the following procedures.<br />

The letter “C” describes a closed valve. See Fig. 17, 18, 29,<br />

<strong>and</strong> 30.<br />

TRANSFER REFRIGERANT FROM PUMPOUT STOR-<br />

AGE TANK TO CHILLER<br />

1. Equalize refrigerant pressure.<br />

a. Use the PIC II terminate lockout function on the<br />

PUMPDOWN LOCKOUT screen, accessed from<br />

69<br />

the CONTROL TEST table to turn on the water<br />

pumps <strong>and</strong> monitor pressures.<br />

If the chilled water <strong>and</strong> condenser water pumps are not<br />

controlled by the PIC II, these pumps must be started <strong>and</strong><br />

stopped manually at the appropriate times during the refrigerant<br />

transfer procedure.<br />

b. Close pumpout unit valves 2, 4, 5, 8, <strong>and</strong> 10, <strong>and</strong><br />

close chiller charging valve 7; open chiller isolation<br />

valves 11, 12, 13, <strong>and</strong> 14 (if present).<br />

c. Open pumpout unit/storage tank valves 3 <strong>and</strong> 6,<br />

open chiller valves 1a <strong>and</strong> 1b.<br />

VALVE 1a 1b 2 3 4 5 6 7 8 10 11 12 13 14<br />

CONDITION C C C C C C<br />

Follow Steps d <strong>and</strong> e carefully to prevent damage from<br />

freeze-up.<br />

d. Slowly open valve 5 to increase chiller pressure to<br />

68 psig 35 psig (141 kPa) for HFC-134a. Feed<br />

refrigerant slowly to prevent freeze up.<br />

e. Open valve 5 fully after the pressure rises above<br />

the freeze point of the refrigerant. Open liquid line<br />

valves 7 <strong>and</strong> 10 until refrigerant pressure<br />

equalizes.<br />

VALVE 1a 1b 2 3 4 5 6 7 8 10 11 12 13 14<br />

CONDITION C C C<br />

2. Transfer the remaining refrigerant.<br />

a. Close valve 5 <strong>and</strong> open valve 4.<br />

VALVE 1a 1b 2 3 4 5 6 7 8 10 11 12 13 14<br />

CONDITION C C C<br />

b. Turn off the chiller water pumps using the CVC/<br />

ICVC (or manually, if necessary).<br />

c. Turn off the pumpout condenser water, <strong>and</strong> turn on<br />

the pumpout compressor to push liquid out of the<br />

storage tank.<br />

d. Close liquid line valve 7.<br />

e. Turn off the pumpout compressor.<br />

f. Close valves 3 <strong>and</strong> 4.<br />

g. Open valves 2 <strong>and</strong> 5.<br />

VALVE 1a 1b 2 3 4 5 6 7 8 10 11 12 13 14<br />

CONDITION C C C C<br />

h. Turn on the pumpout condenser water.<br />

i. Run the pumpout compressor until the pumpout<br />

storage tank pressure reaches 5 psig (34 kPa)<br />

(18 in. Hg [40 kPa absolute] if repairing the tank).<br />

j. Turn off the pumpout compressor.<br />

k. Close valves 1a, 1b, 2, 5, 6, <strong>and</strong> 10.<br />

VALVE 1a 1b 2 3 4 5 6 7 8 10 11 12 13 14<br />

CONDITION C C C C C C C C C C<br />

l. Turn off pumpout condenser water.

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!