10.04.2013 Views

Start-Up, Operation, and Maintenance Instructions

Start-Up, Operation, and Maintenance Instructions

Start-Up, Operation, and Maintenance Instructions

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Ramp Loading — The ramp loading control slows down<br />

the rate at which the compressor loads up. This control can prevent<br />

the compressor from loading up during the short period of<br />

time when the chiller is started <strong>and</strong> the chilled water loop has to<br />

be brought down to CONTROL POINT. This helps reduce<br />

electrical dem<strong>and</strong> charges by slowly bringing the chilled water<br />

to CONTROL POINT. The total power draw during this period<br />

remains almost unchanged.<br />

There are two methods of ramp loading with the PIC II.<br />

Ramp loading can be based on chilled water temperature or on<br />

motor load. Either method is selected from the RAMP__DEM<br />

screen.<br />

1. Temperature ramp loading (TEMP PULLDOWN DEG/<br />

MIN) limits the degrees per minute rate at which either<br />

leaving chilled water or entering chilled water temperature<br />

decreases. This rate is configured by the operator on<br />

the TEMP_CTL screen. The lowest temperature ramp<br />

rate will also be used if chiller power has been off for<br />

3 hours or more (even if the motor ramp load is selected<br />

as the ramp loading method).<br />

2. Motor load ramp loading (LOAD PULLDOWN) limits<br />

the degrees per minute rate at which the compressor motor<br />

current or compressor motor load increases. The<br />

LOAD PULLDOWN rate is configured by the operator<br />

on the RAMP_DEM screen in amps or kilowatts. The<br />

point name is MOTOR LOAD RAMP%/MIN.<br />

If kilowatts is selected for the DEMAND LIMIT SOURCE,<br />

the MOTOR RATED KILOWATTS must be entered (information<br />

found on the chiller Requisition form).<br />

The TEMP PULLDOWN DEG/MIN may be viewed or<br />

modified on the TEMP_CTL screen which is accessed from<br />

the EQUIPMENT SERVICE screen. PULLDOWN RAMP<br />

TYPE, DEMAND LIMIT SOURCE, <strong>and</strong> MOTOR LOAD<br />

RAMP %/MIN may be viewed or modified on the<br />

RAMP_DEM screen.<br />

Capacity Override (Table 4) — Capacity overrides can<br />

prevent some safety shutdowns caused by exceeding the motor<br />

amperage limit, refrigerant low temperature safety limit, motor<br />

high temperature safety limit, <strong>and</strong> condenser high pressure<br />

limit. In all cases there are 2 stages of compressor vane control.<br />

1. The vanes are prevented from opening further, <strong>and</strong> the<br />

status line on the CVC/ICVC indicates the reason for the<br />

override.<br />

2. The vanes are closed until the condition decreases to below<br />

the first step set point. Then the vanes are released to<br />

normal capacity control.<br />

Whenever the motor current dem<strong>and</strong> limit set point<br />

(ACTIVE DEMAND LIMIT) is reached, it activates a capacity<br />

override, again, with a 2-step process. Exceeding 110% of the<br />

rated load amps for more than 30 seconds will initiate a safety<br />

shutdown.<br />

The compressor high lift (surge prevention) set point will<br />

cause a capacity override as well. When the surge prevention<br />

set point is reached, the controller normally will only prevent<br />

the guide vanes from opening. If so equipped, the hot gas bypass<br />

valve will open instead of holding the vanes. See the<br />

Surge Prevention Algorithm section, page 39.<br />

High Discharge Temperature Control — If the<br />

discharge temperature increases above 160 F (71.1 C), the<br />

guide vanes are proportionally opened to increase gas flow<br />

through the compressor. If the leaving chilled water temperature<br />

is then brought 5° F (2.8° C) below the control set point<br />

temperature, the PIC II will bring the chiller into the recycle<br />

mode.<br />

Oil Sump Temperature Control — The oil sump<br />

temperature control is regulated by the PIC II, which uses the<br />

oil heater relay when the chiller is shut down.<br />

36<br />

As part of the pre-start checks executed by the controls, the<br />

oil sump temperature (OIL SUMP TEMP) is compared to the<br />

cooler refrigerant temperature (EVAPORATOR REFRIG<br />

TEMP). If the difference between these 2 temperatures is 50 F<br />

(27.8 C) or less, the start-up will be delayed until the oil temperature<br />

is 50 F (27.8 C) or more. Once this temperature is confirmed,<br />

the start-up continues.<br />

The oil heater relay is energized whenever the chiller compressor<br />

is off <strong>and</strong> the oil sump temperature is less than 140 F<br />

(60.0 C) or the oil sump temperature is less than the cooler refrigerant<br />

temperature plus 53° F (11.7° C). The oil heater is<br />

turned off when the oil sump temperature is either<br />

more than 152 F (66.7 C), or<br />

more than 142 F (61.1 C) <strong>and</strong> more than the cooler<br />

refrigerant temperature plus 55° F (12.8° C).<br />

The oil heater is always off during start-up or when the<br />

compressor is running.<br />

The oil pump is also energized during the time the oil is being<br />

heated (for 60 seconds at the end of every 30 minutes).<br />

Oil Cooler — The oil must be cooled when the compressor<br />

is running. This is accomplished through a small, plate-type<br />

heat exchanger (also called the oil cooler) located behind the<br />

oil pump. The heat exchanger uses liquid condenser refrigerant<br />

as the cooling liquid. Refrigerant thermostatic expansion<br />

valves (TXVs) regulate refrigerant flow to control the oil temperature<br />

entering the bearings. The bulbs for the expansion<br />

valves are strapped to the oil supply line leaving the heat exchanger,<br />

<strong>and</strong> the valves are set to maintain 110 F (43 C).<br />

NOTE: The TXVs are not adjustable. The oil sump temperature<br />

may be at a lower temperature during compressor<br />

operations.<br />

Remote <strong>Start</strong>/Stop Controls — A remote device, such<br />

as a timeclock that uses a set of contacts, may be used to start<br />

<strong>and</strong> stop the chiller. However, the device should not be programmed<br />

to start <strong>and</strong> stop the chiller in excess of 2 or 3 times<br />

every 12 hours. If more than 8 starts in 12 hours (the STARTS<br />

IN 12 HOURS parameter on the MAINSTAT screen) occur, an<br />

excessive starts alarm displays, preventing the chiller from<br />

starting. The operator must press the RESET softkey on the<br />

CVC/ICVC to override the starts counter <strong>and</strong> start the chiller.<br />

If the chiller records 12 starts (excluding recycle starts) in a<br />

sliding 12-hour period, it can be restarted only by pressing the<br />

RESET softkey followed by the LOCAL or CCN<br />

softkey.<br />

This ensures that, if the automatic system is malfunctioning,<br />

the chiller will not repeatedly cycle on <strong>and</strong> off. If the automatic<br />

restart after a power failure option (AUTO RESTART OPTION<br />

on the OPTIONS screen) is not activated when a power failure<br />

occurs, <strong>and</strong> if the remote contact is closed, the chiller will indicate<br />

an alarm because of the loss of voltage.<br />

The contacts for remote start are wired into the starter at terminal<br />

strip J2, terminals 5 <strong>and</strong> 6 on the ISM. See the certified<br />

drawings for further details on contact ratings. The contacts<br />

must have 24 vac dry contact rating.<br />

Spare Safety Inputs — Normally closed (NC) discrete<br />

inputs for additional field-supplied safeties may be wired to the<br />

spare protective limits input channel in place of the factoryinstalled<br />

jumper. (Wire multiple inputs in series.) The opening<br />

of any contact will result in a safety shutdown <strong>and</strong> a display on<br />

the CVC/ICVC. Refer to the certified drawings for safety contact<br />

ratings.<br />

Analog temperature sensors may also be added to the module<br />

(SPARE TEMP #1 <strong>and</strong> #2). The analog temperature sensors<br />

may be configured to cause an alert or alarm on the CCN<br />

network. The alert will not shut the chiller down. Configuring<br />

for alarm state will cause the chiller to shut down.

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!