10.04.2013 Views

Start-Up, Operation, and Maintenance Instructions

Start-Up, Operation, and Maintenance Instructions

Start-Up, Operation, and Maintenance Instructions

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

MECHANICAL STARTER<br />

1. Check all field wiring connections for tightness, clearance<br />

from moving parts, <strong>and</strong> correct connection.<br />

2. Check the contactor(s) to ensure they move freely. Check<br />

the mechanical interlock between contactors to ensure<br />

that 1S <strong>and</strong> 2M contactors cannot be closed at the same<br />

time. Check all other electro-mechanical devices, such as<br />

relays, for free movement. If the devices do not move<br />

freely, contact the starter manufacturer for replacement<br />

components.<br />

3. Reapply starter control power (not main chiller power) to<br />

check the electrical functions.<br />

Ensure the starter (with relay 1CR closed) goes through a<br />

complete <strong>and</strong> proper start cycle.<br />

BENSHAW, INC. Redi<strong>Start</strong> MICRO SOLID-STATE<br />

STARTER<br />

This equipment is at line voltage when AC power is connected.<br />

Pressing the STOP button does not remove voltage.<br />

1. Ensure all wiring connections are properly terminated to<br />

the starter.<br />

2. Verify the ground wire to the starter is installed properly<br />

<strong>and</strong> is sufficient size.<br />

3. Verify the motors are properly grounded to the starter.<br />

4. Verify the proper ac input voltage is brought into the starter<br />

according to the certified drawings.<br />

5. Apply power to the starter<br />

VFD STARTER<br />

1. Turn off unit, tag <strong>and</strong> lock disconnects <strong>and</strong> wait 5 minutes.<br />

2. Verify that the DC voltage is zero.<br />

3. Ensure there is adequate clearance around the drive.<br />

4. Verify that the wiring to the terminal strip <strong>and</strong> power terminals<br />

is correct.<br />

5. Verify that wire size is within the terminal specification<br />

<strong>and</strong> the wires are secure.<br />

6. Inspect the field supplied branch circuit protection is<br />

properly rated <strong>and</strong> installed.<br />

7. Verify that the system is properly grounded.<br />

8. Inspect all liquid cooling connections for leaks.<br />

Oil Charge — The oil charge for the 19XR compressor depends<br />

on the compressor Frame size:<br />

Frame 2 compressor — 5 gal (18.9 L)<br />

Frame 3 compressor — 8 gal (30 L)<br />

Frame 4 compressor — 10 gal (37.8 L)<br />

Frame 5 compressor — 18 gal (67.8 L)<br />

The chiller is shipped with oil in the compressor. When the<br />

sump is full, the oil level should be no higher than the middle<br />

of the upper sight glass, <strong>and</strong> minimum level is the bottom<br />

of the lower sight glass (Fig. 2). If oil is added, it must meet<br />

Carrier’s specification for centrifugal compressor use as described<br />

in the Oil Specification section. Charge the oil through<br />

the oil charging valve located near the bottom of the transmission<br />

housing (Fig. 2). The oil must be pumped from the oil<br />

container through the charging valve due to higher refrigerant<br />

pressure. The pumping device must be able to lift from 0 to<br />

200 psig (0 to 1380 kPa) or above unit pressure. Oil should<br />

only be charged or removed when the chiller is shut down.<br />

Power <strong>Up</strong> the Controls <strong>and</strong> Check the Oil<br />

Heater — Ensure that an oil level is visible in the compressor<br />

before energizing the controls. A circuit breaker in the starter<br />

energizes the oil heater <strong>and</strong> the control circuit. When first<br />

55<br />

powered, the CVC/ICVC should display the default screen<br />

within a short period of time.<br />

The oil heater is energized by powering the control circuit.<br />

This should be done several hours before start-up to minimize<br />

oil-refrigerant migration. The oil heater is controlled by the<br />

PIC II <strong>and</strong> is powered through a contactor in the power panel.<br />

<strong>Start</strong>ers contain a separate circuit breaker to power the heater<br />

<strong>and</strong> the control circuit. This arrangement allows the heater to<br />

energize when the main motor circuit breaker is off for service<br />

work or extended shutdowns. The oil heater relay status (OIL<br />

HEATER RELAY) can be viewed on the COMPRESS table on<br />

the CVC/ICVC. Oil sump temperature can be viewed on the<br />

CVC/ICVC default screen.<br />

SOFTWARE VERSION — The software part number is labeled<br />

on the backside of the CVC/ICVC module. The software<br />

version also appears on the CVC/ICVC configuration screen as<br />

the last two digits of the software part number.<br />

Software Configuration<br />

Do not operate the chiller before the control configurations<br />

have been checked <strong>and</strong> a Control Test has been<br />

satisfactorily completed. Protection by safety controls cannot<br />

be assumed until all control configurations have been<br />

confirmed.<br />

As the 19XR unit is configured, all configuration settings<br />

should be written down. A log, such as the one shown on pages<br />

CL-1 to CL-16, provides a list for configuration values.<br />

Input the Design Set Points — Access the CVC/<br />

ICVC set point screen <strong>and</strong> view/modify the base dem<strong>and</strong> limit<br />

set point, <strong>and</strong> either the LCW set point or the ECW set point.<br />

The PIC II can control a set point to either the leaving or entering<br />

chilled water. This control method is set in the EQUIP-<br />

MENT SERVICE (TEMP_CTL) table.<br />

Input the Local Occupied Schedule (OCCPC01S) —<br />

Access the schedule OCCPC01S screen on the CVC/ICVC<br />

<strong>and</strong> set up the occupied time schedule according to the customer’s<br />

requirements. If no schedule is available, the default is factory<br />

set for 24 hours occupied, 7 days per week including<br />

holidays.<br />

For more information about how to set up a time schedule,<br />

see the Controls section, page 10.<br />

The CCN Occupied Schedule (OCCPC03S) should be configured<br />

if a CCN system is being installed or if a secondary<br />

time schedule is needed.<br />

NOTE: The default CCN Occupied Schedule OCCPC03S is<br />

configured to be unoccupied.<br />

Input Service Configurations — The following configurations<br />

require the CVC/ICVC screen to be in the SER-<br />

VICE portion of the menu.<br />

password<br />

input time <strong>and</strong> date<br />

CVC/ICVC configuration<br />

service parameters<br />

equipment configuration<br />

automated control test<br />

PASSWORD — When accessing the SERVICE tables, a password<br />

must be entered. All CVC/ICVC are initially set for a<br />

password of 1-1-1-1.<br />

INPUT TIME AND DATE — Access the TIME AND DATE<br />

table on the SERVICE menu. Input the present time of day,<br />

date, <strong>and</strong> day of the week. The HOLIDAY TODAY parameter<br />

should only be configured to YES if the present day is a<br />

holiday.

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!