A. MANUAL STOP<br />

Table 11 — CVC/ICVC Primary <strong>and</strong> Secondary Messages <strong>and</strong><br />

Custom Alarm/Alert Messages with Troubleshooting Guides<br />

PRIMARY MESSAGE SECONDARY MESSAGE PROBABLE CAUSE/REMEDY<br />

MANUALLY STOPPED — PRESS CCN OR LOCAL TO START PIC II in OFF mode, press CCN or LOCAL softkey to start unit.<br />

TERMINATE PUMPDOWN MODE TO SELECT CCN OR LOCAL Enter the CONTROL TEST table <strong>and</strong> select TERMINATE LOCKOUT to<br />

unlock compressor.<br />

SHUTDOWN IN PROGRESS COMPRESSOR UNLOADING Chiller unloading before shutdown due to soft/stop feature.<br />

SHUTDOWN IN PROGRESS COMPRESSOR DEENERGIZED Chiller compressor is being comm<strong>and</strong>ed to stop. Water pumps are<br />

deenergized within one minute.<br />

ICE BUILD OPERATION COMPLETE Chiller shutdown from Ice Build operation.<br />

B. READY TO START<br />

PRIMARY MESSAGE SECONDARY MESSAGE PROBABLE CAUSE/REMEDY<br />

READY TO START IN XX MIN UNOCCUPIED MODE Time schedule for PIC II is unoccupied. Chillers will start only when<br />

occupied.<br />

READY TO START IN XX MIN REMOTE CONTACTS OPEN Remote contacts are open. Close contacts to start.<br />

READY TO START IN XX MIN STOP COMMAND IN EFFECT Chiller START/STOP on MAINSTAT manually forced to stop. Release<br />

point to start.<br />

READY TO START IN XX MIN OCCUPIED MODE Chiller timer counting down. Unit ready to start.<br />

READY TO START IN XX MIN REMOTE CONTACTS CLOSED Chiller timer counting down. Unit ready to start. Remote contact enabled<br />

<strong>and</strong> closed.<br />

READY TO START IN XX MIN START COMMAND IN EFFECT Chiller START/STOP on MAINSTAT manually forced to start. Release<br />

value to start under normal control.<br />

READY TO START IN XX MIN RECYCLE RESTART PENDING Chiller in recycle mode.<br />

READY TO START UNOCCUPIED MODE Time schedule for PIC II is unoccupied. Chiller will start when occupied.<br />

Make sure the time <strong>and</strong> date are correct. Change values in TIME AND<br />

DATE screen.<br />

READY TO START REMOTE CONTACTS OPEN Remote contacts have stopped the chiller. Close contacts to start.<br />

READY TO START STOP COMMAND IN EFFECT Chiller START/STOP on MAINSTAT manually forced to stop. Release<br />

point to start.<br />

READY TO START OCCUPIED MODE Chiller timers complete, unit start will commence.<br />

READY TO START REMOTE CONTACTS CLOSED Chiller timer counting down. Unit ready for start.<br />

READY TO START START COMMAND IN EFFECT Chiller START/STOP on MAINSTAT has been manually forced to start.<br />

Chiller will start regardless of time schedule or remote contact status.<br />

STARTUP INHIBITED LOADSHED IN EFFECT CCN loadshed module comm<strong>and</strong>ing chiller to stop.<br />

C. IN RECYCLE SHUTDOWN<br />

PRIMARY MESSAGE SECONDARY MESSAGE PROBABLE CAUSE/REMEDY<br />

RECYCLE RESTART PENDING OCCUPIED MODE Unit in recycle mode, chilled water temperature is not sufficiently<br />

above set point to start.<br />

RECYCLE RESTART PENDING REMOTE CONTACT CLOSED Unit in recycle mode, chilled water temperature is not sufficiently<br />

above set point to start.<br />

RECYCLE RESTART PENDING START COMMAND IN EFFECT Chiller START/STOP on MAINSTAT manually forced to start, chilled<br />

water temperature is not sufficiently above set point to start.<br />

RECYCLE RESTART PENDING ICE BUILD MODE Chiller in ICE BUILD mode. Chilled fluid temperature is satisfied for<br />

ICE BUILD conditions.<br />

78