A. MANUAL STOP<br />
Table 11 — CVC/ICVC Primary <strong>and</strong> Secondary Messages <strong>and</strong><br />
Custom Alarm/Alert Messages with Troubleshooting Guides<br />
PRIMARY MESSAGE SECONDARY MESSAGE PROBABLE CAUSE/REMEDY<br />
MANUALLY STOPPED — PRESS CCN OR LOCAL TO START PIC II in OFF mode, press CCN or LOCAL softkey to start unit.<br />
TERMINATE PUMPDOWN MODE TO SELECT CCN OR LOCAL Enter the CONTROL TEST table <strong>and</strong> select TERMINATE LOCKOUT to<br />
unlock compressor.<br />
SHUTDOWN IN PROGRESS COMPRESSOR UNLOADING Chiller unloading before shutdown due to soft/stop feature.<br />
SHUTDOWN IN PROGRESS COMPRESSOR DEENERGIZED Chiller compressor is being comm<strong>and</strong>ed to stop. Water pumps are<br />
deenergized within one minute.<br />
ICE BUILD OPERATION COMPLETE Chiller shutdown from Ice Build operation.<br />
B. READY TO START<br />
PRIMARY MESSAGE SECONDARY MESSAGE PROBABLE CAUSE/REMEDY<br />
READY TO START IN XX MIN UNOCCUPIED MODE Time schedule for PIC II is unoccupied. Chillers will start only when<br />
occupied.<br />
READY TO START IN XX MIN REMOTE CONTACTS OPEN Remote contacts are open. Close contacts to start.<br />
READY TO START IN XX MIN STOP COMMAND IN EFFECT Chiller START/STOP on MAINSTAT manually forced to stop. Release<br />
point to start.<br />
READY TO START IN XX MIN OCCUPIED MODE Chiller timer counting down. Unit ready to start.<br />
READY TO START IN XX MIN REMOTE CONTACTS CLOSED Chiller timer counting down. Unit ready to start. Remote contact enabled<br />
<strong>and</strong> closed.<br />
READY TO START IN XX MIN START COMMAND IN EFFECT Chiller START/STOP on MAINSTAT manually forced to start. Release<br />
value to start under normal control.<br />
READY TO START IN XX MIN RECYCLE RESTART PENDING Chiller in recycle mode.<br />
READY TO START UNOCCUPIED MODE Time schedule for PIC II is unoccupied. Chiller will start when occupied.<br />
Make sure the time <strong>and</strong> date are correct. Change values in TIME AND<br />
DATE screen.<br />
READY TO START REMOTE CONTACTS OPEN Remote contacts have stopped the chiller. Close contacts to start.<br />
READY TO START STOP COMMAND IN EFFECT Chiller START/STOP on MAINSTAT manually forced to stop. Release<br />
point to start.<br />
READY TO START OCCUPIED MODE Chiller timers complete, unit start will commence.<br />
READY TO START REMOTE CONTACTS CLOSED Chiller timer counting down. Unit ready for start.<br />
READY TO START START COMMAND IN EFFECT Chiller START/STOP on MAINSTAT has been manually forced to start.<br />
Chiller will start regardless of time schedule or remote contact status.<br />
STARTUP INHIBITED LOADSHED IN EFFECT CCN loadshed module comm<strong>and</strong>ing chiller to stop.<br />
C. IN RECYCLE SHUTDOWN<br />
PRIMARY MESSAGE SECONDARY MESSAGE PROBABLE CAUSE/REMEDY<br />
RECYCLE RESTART PENDING OCCUPIED MODE Unit in recycle mode, chilled water temperature is not sufficiently<br />
above set point to start.<br />
RECYCLE RESTART PENDING REMOTE CONTACT CLOSED Unit in recycle mode, chilled water temperature is not sufficiently<br />
above set point to start.<br />
RECYCLE RESTART PENDING START COMMAND IN EFFECT Chiller START/STOP on MAINSTAT manually forced to start, chilled<br />
water temperature is not sufficiently above set point to start.<br />
RECYCLE RESTART PENDING ICE BUILD MODE Chiller in ICE BUILD mode. Chilled fluid temperature is satisfied for<br />
ICE BUILD conditions.<br />
78