10.04.2013 Views

Start-Up, Operation, and Maintenance Instructions

Start-Up, Operation, and Maintenance Instructions

Start-Up, Operation, and Maintenance Instructions

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Owner-Modified CCN Tables — The following EQUIP-<br />

MENT CONFIGURATION screens are described for reference<br />

only.<br />

OCCDEFCS — The OCCDEFCS screen contains the Local<br />

<strong>and</strong> CCN time schedules, which can be modified here or on the<br />

SCHEDULE screen as described previously.<br />

HOLIDAYS — From the HOLIDAYS screen, the days of the<br />

year that holidays are in effect can be configured. See the holiday<br />

paragraphs in the Controls section for more details.<br />

BRODEF — The BRODEF screen defines the start <strong>and</strong> end of<br />

daylight savings time. Enter the dates for the start <strong>and</strong> end of<br />

daylight savings if required for your location. BRODEF also<br />

activates the Broadcast function which enables the holiday<br />

periods that are defined on the CVC/ICVC to take effect.<br />

Other Tables — The CONSUME, NET_OPT, <strong>and</strong> RUN-<br />

TIME screens contain parameters used with a CCN system.<br />

See the applicable CCN manual for more information on these<br />

screens. These tables can only be defined from a CCN Building<br />

Supervisor.<br />

Perform a Control Test — Check the safety controls<br />

status by performing an automated control test. Access the<br />

CONTROL TEST table <strong>and</strong> select a test to be performed function<br />

(Table 9).<br />

The Automated Control Test checks all outputs <strong>and</strong> inputs<br />

for function. In order to successfully proceed with the controls<br />

test, the compressor should be off, no alarms showing, <strong>and</strong> voltage<br />

should be within ±10% of rating plate value. The compressor<br />

can be put in OFF mode by pressing the STOP push-button<br />

on the CVC/ICVC. Each test asks the operator to confirm the<br />

operation is occurring <strong>and</strong> whether or not to continue. If an error<br />

occurs, the operator can try to address the problem as the<br />

test is being done or note the problem <strong>and</strong> proceed to the next<br />

test.<br />

NOTE: Enter guide vane calibration to calibrate guide<br />

input on CCM (Plug J4 upper terminal 9 <strong>and</strong> 10).<br />

NOTE: If during the control test the guide vanes do not open,<br />

verify the low pressure alarm is not active. (An active low<br />

pressure alarm causes the guide vanes to close.)<br />

NOTE: The oil pump test will not energize the oil pump if<br />

cooler pressure is below –5 psig (–35 kPa).<br />

When the control test is finished or the EXIT softkey is<br />

pressed, the test stops, <strong>and</strong> the CONTROL TEST menu displays.<br />

If a specific automated test procedure is not completed,<br />

access the particular control test to test the function when ready.<br />

The CONTROL TEST menu is described in the table below.<br />

CCM Temperature Thermistors Check of all thermistors.<br />

CCM Pressure Transducers Check of all transducers.<br />

Checks operation of pump outputs;<br />

Pump<br />

pumps are activated. Also tests associated<br />

inputs such as flow or pressure.<br />

Discrete outputs<br />

Activation of all on/off outputs individually.<br />

Guide Vane Check of the guide vane operation.<br />

Diffuser Actuator* Check of the diffuser actuator.<br />

Pumpdown prevents the low refrigerant<br />

alarm during evacuation so refrigerant<br />

Pumpdown/Lockout<br />

can be removed form the unit. Also locks<br />

the compressor off <strong>and</strong> starts the water<br />

pumps.<br />

Terminate Lockout<br />

To charge refrigerant <strong>and</strong> enable the<br />

chiller to run after pumpdown lockout.<br />

Guide Vane Calibration Calibrates guide vane input on CCM.<br />

*Diffuser tests function only on size 4 <strong>and</strong> 5 compressor with diffuser control<br />

enabled.<br />

NOTE: During any of the tests, an out-of-range reading will have an asterisk<br />

(*) next to the reading <strong>and</strong> a message will be displayed if you have diffuser<br />

control enabled.<br />

62<br />

COOLER CONDENSER PRESSURE TRANSDUCER<br />

AND WATERSIDE FLOW DEVICE CALIBRATION<br />

(Optional with ICVC inputs available) — Calibration can be<br />

checked by comparing the pressure readings from the<br />

transducer to an accurate refrigeration gage reading. These<br />

readings can be viewed or calibrated from the HEAT_EX<br />

screen on the CVC/ICVC. The transducer can be checked <strong>and</strong><br />

calibrated at 2 pressure points. These calibration points are<br />

0 psig (0 kPa) <strong>and</strong> between 25 <strong>and</strong> 250 psig (173 <strong>and</strong><br />

1724 kPa). To calibrate these transducers:<br />

1. Shut down the compressor, cooler, <strong>and</strong> condenser pumps.<br />

NOTE: There should be no flow through the heat<br />

exchangers.<br />

2. Disconnect the transducer in question from its Schrader<br />

fitting for cooler or condenser transducer calibration. For<br />

oil pressure or flow device calibration keep transducer in<br />

place.<br />

NOTE: If the cooler or condenser vessels are at 0 psig<br />

(0 kPa) or are open to atmospheric pressure, the transducers<br />

can be calibrated for zero without removing the transducer<br />

from the vessel.<br />

3. Access the HEAT_EX screen <strong>and</strong> view the particular<br />

transducer reading (the EVAPORATOR PRESSURE or<br />

CONDENSER PRESSURE parameter on the HEAT_EX<br />

screen). To calibrate oil pressure or waterside flow device,<br />

view the particular reading (CHILLED WATER<br />

DELTA P <strong>and</strong> CONDENSER WATER DELTA P on the<br />

HEAT_EX screen <strong>and</strong> OIL PUMP DELTA P on the<br />

COMPRESS screen). It should read 0 psi (0 kPa). If the<br />

reading is not 0 psi (0 kPa), but within ±5 psi (35 kPa),<br />

the value may be set to zero by pressing the SELECT<br />

softkey while the appropriate transducer parameter is<br />

highlighted on the CVC/ICVC screen. Then press the<br />

ENTER softkey. The value will now go to zero. No high<br />

end calibration is necessary for OIL PUMP DELTA P or<br />

flow devices.<br />

If the transducer value is not within the calibration range,<br />

the transducer returns to the original reading. If the pressure<br />

is within the allowed range (noted above), check the<br />

voltage ratio of the transducer. To obtain the voltage ratio,<br />

divide the voltage (dc) input from the transducer by the<br />

supply voltage signal (displayed in CONTROL TEST<br />

menu in the CCM PRESSURE TRANSDUCERS<br />

screen) or measure across the positive (+ red) <strong>and</strong> negative<br />

(– black) leads of the transducer. For example, the<br />

condenser transducer voltage input is measured at CCM<br />

terminals J2-4 <strong>and</strong> J2-5. The voltage ratio must be between<br />

0.80 <strong>and</strong> 0.11 for the software to allow calibration.<br />

Rotate the waterside flow pressure device from the inlet<br />

nozzle to the outlet nozzle <strong>and</strong> repeat this step. If rotating<br />

the waterside flow device does not allow calibration then<br />

pressurize the transducer until the ratio is within range.<br />

Then attempt calibration again.<br />

4. A high pressure point can also be calibrated between 25<br />

<strong>and</strong> 250 psig (172.4 <strong>and</strong> 1723.7 kPa) by attaching a regulated<br />

250 psig (1724 kPa) pressure (usually from a nitrogen<br />

cylinder). The high pressure point can be calibrated<br />

by accessing the appropriate transducer parameter on the<br />

HEAT_EX screen, highlighting the parameter, pressing<br />

the SELECT softkey, <strong>and</strong> then using the INCREASE<br />

or DECREASE softkeys to adjust the value to the exact<br />

pressure on the refrigerant gage. Press the ENTER<br />

softkey<br />

to finish the calibration. Pressures at high altitude locations<br />

must be compensated for, so the chiller temperature/pressure<br />

relationship is correct.<br />

The PIC II does not allow calibration if the transducer is too<br />

far out of calibration. In this case, a new transducer must be<br />

installed <strong>and</strong> recalibrated.

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!