10.04.2013 Views

Start-Up, Operation, and Maintenance Instructions

Start-Up, Operation, and Maintenance Instructions

Start-Up, Operation, and Maintenance Instructions

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

VERIFY VFD CONFIGURATION AND CHANGE<br />

PARAMETERS IF NECESSARY<br />

IMPORTANT: The VFD controller has been factory configured<br />

for use <strong>and</strong> communications to the Chiller Visual<br />

Controller/International Chiller Visual Controller (CVC/<br />

ICVC). Some parameters are specific to the chiller configuration<br />

<strong>and</strong> will need to be verified prior to operation.<br />

Speed control <strong>and</strong> starting the drive have been disabled at<br />

the VFD keypad. All comm<strong>and</strong> functions must be initiated<br />

from the CVC/ICVC.<br />

Using the Keypad — The keypad display is used to monitor,<br />

view fault history <strong>and</strong> adjust the program of the VFD<br />

microprocessor. It operates in two modes: Monitor mode <strong>and</strong><br />

Program mode:<br />

Use the ↑ <strong>and</strong> ↓ keys to:<br />

Step through the drive parameter menus <strong>and</strong> error log<br />

when the keypad/display is in Program mode.<br />

Increase or decrease a numeric value such as the reference<br />

or parameter value.<br />

Hold down these keys to increase the scroll speed.<br />

Use the ENTER softkey to:<br />

Display a parameter or a selection value in Program<br />

mode.<br />

Save a value.<br />

Move through each monitor display item when in Monitor<br />

mode.<br />

Monitor Mode (Default Mode) — Specific drive conditions<br />

may be monitored on the keypad when in this mode. An LED<br />

will be illuminated next to the description of what is displayed<br />

on the keypad. Use the ENTER softkey to scroll through <strong>and</strong><br />

monitor the following selections:<br />

All LEDs on — Speed request from the CVC/ICVC<br />

Motor Speed<br />

Output Frequency<br />

Output Voltage<br />

Output Current<br />

Program Mode — This mode displays <strong>and</strong> modifies the configuration<br />

parameters of the VFD microprocessor. Particular<br />

parameters, parameter numbers, <strong>and</strong> error log information can<br />

be displayed when in Program mode.<br />

Press the PROGRAM softkey until the PROGRAM LED is<br />

illuminated to enter the Program mode.<br />

Use the ↑ <strong>and</strong> ↓ keys to move through the menus<br />

Press ENTER softkey to select the desired menu.<br />

Press ↑ <strong>and</strong> ↓ keys to move through following parameters.<br />

P.nnn — General Parameters<br />

U.nnn — Vector Control Parameters*<br />

H.nnn — Volts/Hertz Control Parameters<br />

R.nnn — RMI Remote Monitor Interface<br />

Parameters<br />

E.nnn — Error Log (See fault codes)<br />

*Vector control is not used in this configuration.<br />

Press ENTER softkey to select a parameter menu screen.<br />

Press ↑ <strong>and</strong> ↓ keys to adjust the selected parameter.<br />

Press the PROGRAM softkey until the PROGRAM LED<br />

turns off to exit the program.<br />

Changing parameters may adversely affect chiller<br />

operation.<br />

58<br />

Accessing Password Protected Parameters — Although the<br />

VFD controller has been preconfigured as the factory, the user<br />

will need to be able to access the parameters to verify the job<br />

specific parameters are correct, tune the controller or correct a<br />

problem. The two passwords protecting the VFD configuration<br />

are Parameter Set Display password <strong>and</strong> Program Disable<br />

password. The Parameter Set Display password restricts viewing.<br />

P.nnn parameters above 007 <strong>and</strong> all H.nnn <strong>and</strong> R.nnn<br />

screens. The password can be accessed at parameter P.006 <strong>and</strong><br />

will switch between enabled <strong>and</strong> disabled each time the password<br />

107 is entered. The Program Disable password restricts<br />

the changing of the drive parameter set. To enable or disable<br />

changes select parameter P.051 <strong>and</strong> enter the password 26.<br />

NOTE: Some of the parameters can be changed only when the<br />

drive is stopped.<br />

It is the operator’s responsibility to distribute access to the<br />

passwords. Carrier is not responsible for unauthorized<br />

access violations within the operator’s organization. Failure<br />

to observe this warning could result in bodily injury.<br />

See the Initial <strong>Start</strong>-<strong>Up</strong> Checklist section for VFD Job Specific<br />

Configuration table. For job specific parameters see inside of<br />

the VFD enclosure door, next to the keypad. Refer to the VFD<br />

Configuration table for the entire list of parameters.<br />

Restoring the default parameter P.050 will require all the<br />

Carrier default parameters to be restored manually.<br />

VFD CHILLER FIELD SET UP AND VERIFICATION<br />

Label Locations — Verify the following labels have been<br />

installed properly <strong>and</strong> match the chiller requisition:<br />

Surge parameters — Located inside the control panel.<br />

Chiller identification nameplate — Located on the right<br />

side of the control panel.<br />

VFD Parameter — Located to the right of the VFD controller<br />

keypad on the VFD module.<br />

VFD Nameplate — Located on the right side of the VFD<br />

as viewed from its front.<br />

Record all nameplate information on the Reliance Configuration<br />

sheet.<br />

Drive Protection <strong>and</strong> Other Incoming Wiring<br />

1. Verify that the branch disconnects or other local disconnects<br />

are open <strong>and</strong> properly tagged out.<br />

2. Verify that the branch circuit protection <strong>and</strong> AC input<br />

wiring to the VFD are in accordance with NEC/CEC<br />

(National Electrical Code/California Energy Commission)<br />

<strong>and</strong> all other local codes.<br />

3. Verify that the fuses are per the field wiring diagram.<br />

4. Verify that the incoming source does not exceed 85 kA.<br />

5. Verify the power lugs in the VFD <strong>and</strong> branch protection<br />

are properly secured. Inspect the ground cable <strong>and</strong> ensure<br />

it is properly connected at the branch <strong>and</strong> to the ground<br />

lug in the VFD.<br />

6. Verify the conduit for the power wiring in securely connected<br />

to the VFD flanged cover <strong>and</strong> runs continuously to<br />

the branch protection.<br />

7. Verify that the incoming <strong>and</strong> outgoing wires have been<br />

properly connected inside of the reactor enclosure if a<br />

separate line reactor has been added to the chiller.<br />

8. Ensure the control <strong>and</strong> signal wires connected to the chiller<br />

controller or the VFD are in separate conduit.

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!