I. CHILLER PROTECT LIMIT FAULTS (cont)<br />

STATE<br />

246<br />

247<br />

248<br />

249<br />

250<br />

251<br />

252<br />

253<br />

PRIMARY<br />

MESSAGE<br />

PROTECTIVE<br />

LIMIT<br />

PROTECTIVE<br />

LIMIT<br />

PROTECTIVE<br />

LIMIT<br />

PROTECTIVE<br />

LIMIT<br />

PROTECTIVE<br />

LIMIT<br />

PROTECTIVE<br />

LIMIT<br />

PROTECTIVE<br />

LIMIT<br />

PROTECTIVE<br />

LIMIT<br />

Table 11 — CVC/ICVC Primary <strong>and</strong> Secondary Messages <strong>and</strong><br />

Custom Alarm/Alert Messages with Troubleshooting Guides (cont)<br />

*[LIMIT] is shown on the CVC/ICVC as the temperature, pressure, voltage, etc., set point predefined or selected by the operator as an override,<br />

alert, or alarm condition. [VALUE] is the actual pressure, temperature, voltage, etc., at which the control tripped.<br />

J. CHILLER ALERTS<br />

STATE<br />

PRIMARY<br />

MESSAGE<br />

SECONDARY<br />

MESSAGE<br />

INVALID DIFFUSER<br />

CONFIG<br />

DIFFUSER POSITION<br />

FAULT<br />

SPARE TEMPERATURE<br />

#1<br />

SPARE TEMPERATURE<br />

#2<br />

REFRIGERANT LEAK<br />

SENSOR<br />

ISM CONFIG<br />

CONFLICT<br />

ISM CONFIG<br />

CONFLICT<br />

GUIDE VANE<br />

CALIBRATION<br />

140 SENSOR ALERT LEAVING COND<br />

WATER TEMP<br />

141 SENSOR ALERT ENTERING COND<br />

WATER TEMP<br />

142<br />

143<br />

144<br />

145<br />

146<br />

147<br />

148<br />

LOW OIL PRESSURE<br />

ALERT<br />

AUTORESTART<br />

PENDING<br />

AUTORESTART<br />

PENDING<br />

AUTORESTART<br />

PENDING<br />

AUTORESTART<br />

PENDING<br />

AUTORESTART<br />

PENDING<br />

AUTORESTART<br />

PENDING<br />

ALARM MESSAGE<br />

PRIMARY CAUSE<br />

246->Diffuser Control Invalid<br />

Configuration:<br />

Check SETUP2 Entries.<br />

247->Diffuser Position Fault:<br />

Check Guide Vane <strong>and</strong> Diffuser<br />

Actuators<br />

248->Spare Temperature #1<br />

[VALUE] exceeded limit of<br />

[LIMIT]*.<br />

249->Spare Temperature #2<br />

[VALUE] exceeded limit of<br />

[LIMIT]*.<br />

250->Refrigerant Leak Sensor<br />

[VALUE] exceeded Limit of<br />

[LIMIT]*.<br />

251->ISM Config Conflict (ISM<br />

<strong>Up</strong>loaded); Verify to Reset Alarm<br />

252->ISM Config Conflict (ISM<br />

Downloaded); Verify to Reset<br />

Alarm<br />

253->Guide Vane Fault [VALUE].<br />

Check Calibration.<br />

83<br />

ADDITIONAL<br />

CAUSE/REMEDY<br />

Check diffuser/guide vane schedule.<br />

Check rotating stall transducer wiring <strong>and</strong><br />

accuracy.<br />

Check diffuser schedule.<br />

Check for proper operation of diffuser actuator<br />

<strong>and</strong> inlet guide vane actuator.<br />

Check diffuser coupling.<br />

Check inlet guide vane operation.<br />

Check inlet guide vane calibration.<br />

Check diffuser/inlet guide vane schedule.<br />

Check diffuser mechanical set-up for proper<br />

orientation.<br />

If not using variable diffuser, check that the<br />

option has not been enabled.<br />

The refrigerant leak detector’s output wired to<br />

J5-5 <strong>and</strong> J5-6 on the CCM module has<br />

reached the alarm limit.<br />

Check leak detector <strong>and</strong> for leaks.<br />

Confirm valid settings in ISM_CONF screen.<br />

Confirm valid settings in ISM_CONF screen.<br />

Enter Control Test <strong>and</strong> execute Guide Vane<br />

Calibration. Check guide vane feedback (terminals<br />

J4-9 <strong>and</strong> J4-10) on the CCM module.<br />

SECONDARY ALARM MESSAGE<br />

ADDITIONAL<br />

MESSAGE<br />

PRIMARY CAUSE<br />

CAUSE/REMEDY<br />

140->Sensor Fault:<br />

Check sensor resistance or voltage drop.<br />

Check Leaving Cond Water<br />

Sensor<br />

Check for proper wiring.<br />

141->Sensor Fault:<br />

Check sensor resistance or voltage drop.<br />

Check Entering Cond Water<br />

Sensor<br />

Check for proper wiring.<br />

CHECK OIL FILTER 142->Low Oil Pressure Alert. Check for partially or closed shut-off valves.<br />

Check Oil Filter.<br />

Check oil filter.<br />

Check oil pump <strong>and</strong> power supply.<br />

Check oil level.<br />

Check for foaming oil at start-up.<br />

Check transducer wiring <strong>and</strong> accuracy.<br />

LINE PHASE<br />

143->Line Phase Loss Power loss has been detected in any phase.<br />

LOSS<br />

Chiller automatically restarting.<br />

LINE VOLTAGE 144->Single Cycle Line A drop in line voltage has been detected within<br />

DROP OUT<br />

Voltage Dropout<br />

2 voltage cycles. Chiller automatically restarting if<br />

Autorestart option is enabled.<br />

HIGH LINE<br />

145>Line Overvoltage — Check line power.<br />

VOLTAGE<br />

Average Line Volt [VALUE]<br />

LOW LINE<br />

146->Line Undervoltage — Check line power.<br />

VOLTAGE<br />

Average Line Volt [VALUE]<br />

STARTER MODULE 147-><strong>Start</strong>er Module Power- ISM has detected a hardware fault <strong>and</strong> has reset.<br />

RESET<br />

On Reset When Running Chiller automatically restarting.<br />

POWER LOSS 148->Control Power-Loss<br />

When Running<br />

Check control power.