10.04.2013 Views

Start-Up, Operation, and Maintenance Instructions

Start-Up, Operation, and Maintenance Instructions

Start-Up, Operation, and Maintenance Instructions

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Check Optional Pumpout System Controls<br />

<strong>and</strong> Compressor — Controls include an on/off switch,<br />

a 3-amp fuse, the compressor overloads, an internal thermostat,<br />

a compressor contactor, <strong>and</strong> a refrigerant high pressure cutout.<br />

The high pressure cutout is factory set to open at 161 psig<br />

(1110 kPa) <strong>and</strong> reset at 130 psig (896 kPa). Ensure the watercooled<br />

condenser has been connected. Loosen the compressor<br />

holddown bolts to allow free spring travel. Open the compressor<br />

suction <strong>and</strong> discharge the service valves. Ensure oil is visible<br />

in the compressor sight glass. Add oil if necessary.<br />

See the Pumpout <strong>and</strong> Refrigerant Transfer Procedures <strong>and</strong><br />

Optional Pumpout System <strong>Maintenance</strong> sections, pages 67 <strong>and</strong><br />

75, for details on the transfer of refrigerant, oil specifications,<br />

etc.<br />

Table 9 — Control Test Menu Functions<br />

TESTS TO BE<br />

DEVICES TESTED<br />

PERFORMED<br />

1. CCM Thermistors Entering Chilled Water<br />

Evaporator Refrigerant Temperature<br />

(ICVC only)<br />

Leaving Chilled Water<br />

Entering Condenser Water<br />

Leaving Condenser Water<br />

Remote Reset Sensor<br />

Comp Discharge Temp<br />

Oil Sump Temp<br />

Comp Motor Winding Temp<br />

Space Temperature 1<br />

Space Temperature 2<br />

2. CCM Pressure<br />

Evaporator Pressure<br />

Transducers<br />

Condenser Pressure<br />

Oil Pump Delta P<br />

Condenser Water Delta P<br />

Transducer Voltage Ref<br />

3. Pumps Chilled Water — Confirm pressure<br />

Condenser Water — Confirm<br />

Delta P<br />

4. Discrete Outputs Oil Heater Relay<br />

Hot Gas Bypass Relay<br />

Tower Fan Relay Low<br />

Tower Fan Relay High<br />

Alarm Relay<br />

Shunt Trip Relay<br />

5. Guide Vane Actuator Open/Close<br />

6. Diffuser Actuator Open/Close<br />

7. Pumpdown Lockout When using pumpdown/lockout,<br />

observe freeze up precautions when<br />

removing charge:<br />

Instructs operator which valves to<br />

close <strong>and</strong> when.<br />

<strong>Start</strong>s chilled water <strong>and</strong> condenser<br />

water pumps <strong>and</strong> confirms flows.<br />

Monitors<br />

Evaporator pressure<br />

Condenser pressure<br />

Evaporator temperature during<br />

pumpout procedures<br />

Turns pumps off after pumpdown.<br />

Locks out compressor.<br />

8 Terminate Lockout <strong>Start</strong>s pumps <strong>and</strong> monitors flows.<br />

Instructs operator which valves to<br />

open <strong>and</strong> when.<br />

Monitors<br />

Evaporator pressure<br />

Condenser pressure<br />

Evaporator temperature during<br />

charging process<br />

Terminates compressor lockout.<br />

63<br />

High Altitude Locations — Because the chiller is initially<br />

calibrated at sea level, it is necessary to recalibrate the<br />

pressure transducers if the chiller has been moved to a high altitude<br />

location. See the calibration procedure in the Troubleshooting<br />

Guide section.<br />

Charge Refrigerant into Chiller<br />

The transfer, addition, or removal of refrigerant in spring<br />

isolated chillers may place severe stress on external piping<br />

if springs have not been blocked in both up <strong>and</strong> down<br />

directions.<br />

Always operate the condenser <strong>and</strong> chilled water pumps<br />

during charging operations to prevent freeze-ups.<br />

The st<strong>and</strong>ard 19XR chiller is shipped with the refrigerant<br />

already charged in the vessels. However, the 19XR may be ordered<br />

with a nitrogen holding charge of 15 psig (103 kPa).<br />

Evacuate the nitrogen from the entire chiller, <strong>and</strong> charge the<br />

chiller from refrigerant cylinders.<br />

CHILLER EQUALIZATION WITHOUT A PUMPOUT<br />

UNIT<br />

When equalizing refrigerant pressure on the 19XR chiller<br />

after service work or during the initial chiller start-up, do<br />

not use the discharge isolation valve to equalize. Either the<br />

motor cooling isolation valve or the charging hose (connected<br />

between the pumpout valves on top of the cooler<br />

<strong>and</strong> condenser) should be used as the equalization valve.<br />

To equalize the pressure differential on a refrigerant isolated<br />

19XR chiller, use the terminate lockout function of the CON-<br />

TROL TEST on the SERVICE menu. This helps to turn on<br />

pumps <strong>and</strong> advises the operator on proper procedures.<br />

The following steps describe how to equalize refrigerant<br />

pressure in an isolated 19XR chiller without a pumpout unit.<br />

1. Access terminate lockout function on the CONTROL<br />

TEST screen.<br />

2. IMPORTANT: Turn on the chilled water <strong>and</strong> condenser<br />

water pumps to prevent freezing.<br />

3. Slowly open the refrigerant cooling isolation valve. The<br />

chiller cooler <strong>and</strong> condenser pressures will gradually<br />

equalize. This process takes approximately 15 minutes.<br />

4. Once the pressures have equalized, the cooler isolation<br />

valve, the condenser isolation valve, <strong>and</strong> the hot gas isolation<br />

valve may now be opened. Refer to Fig. 29 <strong>and</strong> 30,<br />

for the location of the valves.<br />

Whenever turning the discharge isolation valve, be sure to<br />

reattach the valve locking device. This prevents the valve<br />

from opening or closing during service work or during<br />

chiller operation.

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!