- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -- - - - - - - - - - - - - - - - - - -<br />

19XR, XRV PIC II SETUP1 TABLE CONFIGURATION SHEET<br />

DESCRIPTION RANGE UNITS DEFAULT VALUE<br />

Comp Motor Temp Override 150 to 200 DEG F 200<br />

Cond Press Override 90 to 165 PSI 125<br />

Comp Discharge Alert 125 to 200 DEG F 200<br />

Comp Thrust Brg Alert 165 to 185 DEG F 175<br />

Chilled Medium 0/1 WATER/BRINE WATER<br />

Chilled Water Deadb<strong>and</strong> .5 to 2.0 ˆF 1.0<br />

Evap Refrig Trippoint 0.0 to 40.0 DEG F 33<br />

Refrig Override Delta T 2.0 to 5.0 ˆF 3<br />

Condenser Freeze Point –20 to 35 DEG F 34<br />

Evap Flow Delta P Cutout 0.5 to 50.0 PSI 5.0<br />

Cond Flow Delta P Cutout 0.5 to 50.0 PSI 5.0<br />

Water Flow Verify Time 0.5 to 5 MIN 5<br />

Oil Press Verify Time 15 to 300 SEC 40<br />

Recycle Control<br />

Restart Delta T 2.0 to 10.0 DEG F 5<br />

Shutdown Delta T 0.5 to 4.0 DEG F 1<br />

SPARE ALERT/ALARM ENABLE<br />

Disable=0, Lo=1/3, Hi=2/4<br />

Spare Temp #1 Enable 0 to 4 0<br />

Spare Temp #1 Limit –40 to 245 DEG F 245<br />

Spare Temp #2 Enable 0 to 4 0<br />

Spare Temp #2 Limit –40 to 245 DEG F 245<br />

CL-7