- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -- - - - - - - - - - - - - - - - - - -<br />
19XR, XRV PIC II SETUP1 TABLE CONFIGURATION SHEET<br />
DESCRIPTION RANGE UNITS DEFAULT VALUE<br />
Comp Motor Temp Override 150 to 200 DEG F 200<br />
Cond Press Override 90 to 165 PSI 125<br />
Comp Discharge Alert 125 to 200 DEG F 200<br />
Comp Thrust Brg Alert 165 to 185 DEG F 175<br />
Chilled Medium 0/1 WATER/BRINE WATER<br />
Chilled Water Deadb<strong>and</strong> .5 to 2.0 ˆF 1.0<br />
Evap Refrig Trippoint 0.0 to 40.0 DEG F 33<br />
Refrig Override Delta T 2.0 to 5.0 ˆF 3<br />
Condenser Freeze Point –20 to 35 DEG F 34<br />
Evap Flow Delta P Cutout 0.5 to 50.0 PSI 5.0<br />
Cond Flow Delta P Cutout 0.5 to 50.0 PSI 5.0<br />
Water Flow Verify Time 0.5 to 5 MIN 5<br />
Oil Press Verify Time 15 to 300 SEC 40<br />
Recycle Control<br />
Restart Delta T 2.0 to 10.0 DEG F 5<br />
Shutdown Delta T 0.5 to 4.0 DEG F 1<br />
SPARE ALERT/ALARM ENABLE<br />
Disable=0, Lo=1/3, Hi=2/4<br />
Spare Temp #1 Enable 0 to 4 0<br />
Spare Temp #1 Limit –40 to 245 DEG F 245<br />
Spare Temp #2 Enable 0 to 4 0<br />
Spare Temp #2 Limit –40 to 245 DEG F 245<br />
CL-7