10.04.2013 Views

Start-Up, Operation, and Maintenance Instructions

Start-Up, Operation, and Maintenance Instructions

Start-Up, Operation, and Maintenance Instructions

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

(see wiring diagrams or certified drawings). The temperature<br />

sensor must be wired to terminal J4-13 <strong>and</strong> J4-14. To configure<br />

Reset Type 2, enter the temperature of the remote sensor at the<br />

point where no temperature reset will occur (REMOTE TEMP<br />

–> NO RESET). Next, enter the temperature at which the full<br />

amount of reset will occur (REMOTE TEMP –> FULL<br />

RESET). Then, enter the maximum amount of reset required to<br />

operate the chiller (DEGREES RESET). Reset Type 2 can now<br />

be activated.<br />

RESET TYPE 3 — Reset Type 3 is an automatic chilled water<br />

temperature reset based on cooler temperature difference.<br />

Reset Type 3 adds ± 30° F (± 16° C) based on the temperature<br />

difference between the entering <strong>and</strong> leaving chilled water<br />

temperature.<br />

To configure Reset Type 3, enter the chilled water temperature<br />

difference (the difference between entering <strong>and</strong> leaving<br />

chilled water) at which no temperature reset occurs (CHW<br />

DELTA T –> NO RESET). This chilled water temperature difference<br />

is usually the full design load temperature difference.<br />

Next, enter the difference in chilled water temperature at which<br />

the full amount of reset occurs (CHW DELTA T –> FULL RE-<br />

SET). Finally, enter the amount of reset (DEGREES RESET).<br />

Reset Type 3 can now be activated.<br />

Dem<strong>and</strong> Limit Control Option — The dem<strong>and</strong> limit<br />

control option (20 mA DEMAND LIMIT OPT) is externally<br />

controlled by a 4 to 20 mA or 1 to 5 vdc signal from an energy<br />

management system (EMS). The option is set up on the<br />

RAMP_DEM screen. When enabled, 4 mA is the 100% dem<strong>and</strong><br />

set point with an operator-configured minimum dem<strong>and</strong><br />

at a 20 mA set point (DEMAND LIMIT AT 20 mA).<br />

The auto. dem<strong>and</strong> limit is hardwired to terminals J5-1 (–)<br />

<strong>and</strong> J5-2 (+) on the CCM. Switch setting number 1 on SW2<br />

will determine the type of input signal. With the switch set at<br />

the ON position the input is configured for an externally powered<br />

4 to 20 mA signal. With the switch in the OFF position the<br />

input is configured for an external 1 to 5 vdc signal.<br />

Surge Prevention Algorithm (Fixed Speed<br />

Chiller) — This is an operator-configurable feature that can<br />

determine if lift conditions are too high for the compressor <strong>and</strong><br />

then take corrective action. Lift is defined as the difference between<br />

the pressure at the impeller eye <strong>and</strong> at the impeller<br />

discharge. The maximum lift a particular impeller wheel can<br />

perform varies with the gas flow across the impeller <strong>and</strong> the<br />

size of the wheel.<br />

A surge condition occurs when the lift becomes so high the<br />

gas flow across the impeller reverses. This condition can eventually<br />

cause chiller damage. The surge prevention algorithm<br />

notifies the operator that chiller operating conditions are marginal<br />

<strong>and</strong> to take action to help prevent chiller damage such as<br />

lowering entering condenser water temperature.<br />

The surge prevention algorithm first determines if corrective<br />

action is necessary. The algorithm checks 2 sets of operator-configured<br />

data points, the minimum load points (MIN.<br />

LOAD POINT [T1,P1]) <strong>and</strong> the full load points (FULL LOAD<br />

POINT [T2,P2]). These points have default settings as defined<br />

on the OPTIONS screen or on Table 4.<br />

The surge prevention algorithm function <strong>and</strong> settings are<br />

graphically displayed in Fig. 21 <strong>and</strong> 22. The two sets of load<br />

points on the graph (default settings are shown) describe a line<br />

the algorithm uses to determine the maximum lift of the compressor.<br />

When the actual differential pressure between the cooler<br />

<strong>and</strong> condenser <strong>and</strong> the temperature difference between the<br />

entering <strong>and</strong> leaving chilled water are above the line on the<br />

graph (as defined by the minimum <strong>and</strong> full load points), the algorithm<br />

goes into a corrective action mode. If the actual values<br />

are below the line <strong>and</strong> outside of the deadb<strong>and</strong> region, the algorithm<br />

takes no action. When the point defined by the ACTIVE<br />

DELTA P <strong>and</strong> ACTIVE DELTA T, moves from the region<br />

39<br />

where the HOT GAS BYPASS/SURGE PREVENTION is off,<br />

the point must pass through the deadb<strong>and</strong> region to the line<br />

determined by the configured values before the HOT GAS<br />

BYPASS/SURGE PREVENTION will be turned on. As the<br />

point moves from the region where the HOT GAS BYPASS/<br />

SURGE PREVENTION is on, the point must pass through the<br />

deadb<strong>and</strong> region before the HOT GAS BYPASS/SURGE<br />

PREVENTION is turned off. Information on modifying the default<br />

set points of the minimum <strong>and</strong> full load points may be<br />

found in the Input Service Configurations section, page 55.<br />

The state of the surge/hot gas bypass algorithm on the<br />

HEAT_EX DISPLAY SCREEN (Surge/HGBP Active?).<br />

Corrective action can be taken by making one of 2 choices.<br />

If a hot gas bypass line is present <strong>and</strong> the hot gas option is<br />

selected on the OPTIONS table (SURGE LIMIT/HGBP<br />

OPTION is set to 1), the hot gas bypass valve can be energized.<br />

If the hot gas bypass option is not selected (SURGE LIMIT/<br />

HGBP OPTION is set to 0), hold the guide vanes. See Table 4,<br />

ECW<br />

LEGEND<br />

— Entering Chilled Water<br />

HGBP — Hot Gas Bypass<br />

LCW — Leaving Chilled Water<br />

∆P = (Condenser Psi) – (Cooler Psi)<br />

∆T = (ECW) – (LCW)<br />

Fig. 21 — 19XR Hot Gas Bypass/Surge<br />

Prevention with Default English Settings<br />

LEGEND<br />

ECW — Entering Chilled Water<br />

HGBP — Hot Gas Bypass<br />

LCW — Leaving Chilled Water<br />

∆P = (Condenser kPa) – (Cooler kPa)<br />

∆T = (ECW) – (LCW)<br />

Fig. 22 — 19XR Hot Gas Bypass/Surge<br />

Prevention with Default Metric Settings

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!