J. CHILLER ALERTS (cont)<br />

Table 11 — CVC/ICVC Primary <strong>and</strong> Secondary Messages <strong>and</strong><br />

Custom Alarm/Alert Messages with Troubleshooting Guides (cont)<br />

STATE<br />

PRIMARY<br />

MESSAGE<br />

SECONDARY<br />

MESSAGE<br />

ALARM MESSAGE<br />

PRIMARY CAUSE<br />

ADDITIONAL<br />

CAUSE/REMEDY<br />

149 SENSOR ALERT HIGH DISCHARGE 149->Comp Discharge Temp Check sensor resistance or voltage drop.<br />

TEMP<br />

[VALUE] exceeded limit of Check for proper wiring.<br />

[LIMIT]*.<br />

Check for proper condenser flow <strong>and</strong><br />

temperature.<br />

Check for high lift or low load.<br />

Check for proper inlet guide vane <strong>and</strong> diffuser<br />

actuator operation (Size 5 compressor Only).<br />

Check for fouled tubes or noncondensables in<br />

the refrigerant system.<br />

150 SENSOR ALERT HIGH BEARING<br />

TEMPERATURE<br />

150->Comp Thrust Bearing<br />

Temp [VALUE] exceeded limit<br />

Check sensor resistance or voltage drop.<br />

Check for proper wiring.<br />

of [LIMIT]*.<br />

Check for partially closed service valves.<br />

Check oil cooler TXV.<br />

Check oil filter.<br />

Check oil level.<br />

151 CONDENSER<br />

PRESSURE ALERT<br />

PUMP RELAY<br />

ENERGIZED<br />

151->High Condenser<br />

Pressure [VALUE]: Pump<br />

Check sensor wiring <strong>and</strong> accuracy.<br />

Check condenser flow <strong>and</strong> fluid<br />

Energized to Reduce temperature.<br />

Pressure.<br />

Check for fouled tubes. This alarm is not<br />

caused by the High Pressure Switch.<br />

152 RECYCLE<br />

EXCESSIVE RECYCLE 152->Excessive recycle starts. Chiller load is too low to keep compressor on<br />

ALERT<br />

STARTS<br />

line <strong>and</strong> there has been more than<br />

5 starts in 4 hours. Increase chiller load,<br />

adjust hot gas bypass, increase RECYCLE<br />

RESTART DELTA T from SETUP1 Screen.<br />

153 no message:<br />

no message;<br />

153->Lead/Lag Disabled: Illegal chiller address configuration in Lead/<br />

ALERT only<br />

ALERT only<br />

Duplicate Chiller Address; Lag screen. Both chillers require a different<br />

Check Configuration<br />

address.<br />

154 POTENTIAL<br />

COND PRESS/TEMP 154->Condenser freeze up The condenser pressure transducer is read-<br />

FREEZE-UP<br />

TOO LOW<br />

prevention<br />

ing a pressure that could freeze the condenser<br />

tubes.<br />

Check for condenser refrigerant leaks.<br />

Check fluid temperature.<br />

Check sensor wiring <strong>and</strong> accuracy.<br />

Place the chiller in PUMPDOWN mode if the<br />

vessel is evacuated.<br />

155 OPTION SENSOR<br />

FAULT<br />

REMOTE RESET<br />

SENSOR<br />

155->Sensor Fault/Option<br />

Disabled:<br />

Remote Reset Sensor<br />

Check sensor resistance or voltage drop.<br />

Check for proper wiring.<br />

156 OPTION SENSOR<br />

FAULT<br />

AUTO CHILLED<br />

WATER RESET<br />

156->Sensor Fault/Option<br />

Disabled:<br />

Auto Chilled Water Reset<br />

Check sensor resistance or voltage drop.<br />

Check for proper wiring.<br />

157 OPTION SENSOR<br />

FAULT<br />

AUTO DEMAND<br />

LIMIT INPUT<br />

157->Sensor Fault/Option<br />

Disabled:<br />

Auto Dem<strong>and</strong> Limit Input<br />

Check sensor resistance or voltage drop.<br />

Check for proper wiring.<br />

158 SENSOR ALERT SPARE TEMPERATURE<br />

#1<br />

158->Spare Temperature #1<br />

[VALUE] exceeded limit of<br />

[LIMIT].*<br />

Check sensor resistance or voltage drop.<br />

Check for proper wiring.<br />

159 SENSOR ALERT SPARE TEMPERATURE<br />

#2<br />

159->Spare Temperature #2<br />

[VALUE] exceeded limit of<br />

[LIMIT].*<br />

Check sensor resistance or voltage drop.<br />

Check for proper wiring.<br />

160 DIFFUSER<br />

DIFFUSER<br />

160->Diffuser Position Alert; Check diffuser configuration in SETUP2<br />

ALERT<br />

POSITION<br />

Check Diffuser Configuration. screen.<br />

*[LIMIT] is shown on the CVC/ICVC as the temperature, pressure, voltage, etc., set point predefined or selected by the operator as an override,<br />

alert, or alarm condition. [VALUE] is the actual pressure, temperature, voltage, etc., at which the control tripped.<br />

84