J. CHILLER ALERTS (cont)<br />
Table 11 — CVC/ICVC Primary <strong>and</strong> Secondary Messages <strong>and</strong><br />
Custom Alarm/Alert Messages with Troubleshooting Guides (cont)<br />
STATE<br />
PRIMARY<br />
MESSAGE<br />
SECONDARY<br />
MESSAGE<br />
ALARM MESSAGE<br />
PRIMARY CAUSE<br />
ADDITIONAL<br />
CAUSE/REMEDY<br />
149 SENSOR ALERT HIGH DISCHARGE 149->Comp Discharge Temp Check sensor resistance or voltage drop.<br />
TEMP<br />
[VALUE] exceeded limit of Check for proper wiring.<br />
[LIMIT]*.<br />
Check for proper condenser flow <strong>and</strong><br />
temperature.<br />
Check for high lift or low load.<br />
Check for proper inlet guide vane <strong>and</strong> diffuser<br />
actuator operation (Size 5 compressor Only).<br />
Check for fouled tubes or noncondensables in<br />
the refrigerant system.<br />
150 SENSOR ALERT HIGH BEARING<br />
TEMPERATURE<br />
150->Comp Thrust Bearing<br />
Temp [VALUE] exceeded limit<br />
Check sensor resistance or voltage drop.<br />
Check for proper wiring.<br />
of [LIMIT]*.<br />
Check for partially closed service valves.<br />
Check oil cooler TXV.<br />
Check oil filter.<br />
Check oil level.<br />
151 CONDENSER<br />
PRESSURE ALERT<br />
PUMP RELAY<br />
ENERGIZED<br />
151->High Condenser<br />
Pressure [VALUE]: Pump<br />
Check sensor wiring <strong>and</strong> accuracy.<br />
Check condenser flow <strong>and</strong> fluid<br />
Energized to Reduce temperature.<br />
Pressure.<br />
Check for fouled tubes. This alarm is not<br />
caused by the High Pressure Switch.<br />
152 RECYCLE<br />
EXCESSIVE RECYCLE 152->Excessive recycle starts. Chiller load is too low to keep compressor on<br />
ALERT<br />
STARTS<br />
line <strong>and</strong> there has been more than<br />
5 starts in 4 hours. Increase chiller load,<br />
adjust hot gas bypass, increase RECYCLE<br />
RESTART DELTA T from SETUP1 Screen.<br />
153 no message:<br />
no message;<br />
153->Lead/Lag Disabled: Illegal chiller address configuration in Lead/<br />
ALERT only<br />
ALERT only<br />
Duplicate Chiller Address; Lag screen. Both chillers require a different<br />
Check Configuration<br />
address.<br />
154 POTENTIAL<br />
COND PRESS/TEMP 154->Condenser freeze up The condenser pressure transducer is read-<br />
FREEZE-UP<br />
TOO LOW<br />
prevention<br />
ing a pressure that could freeze the condenser<br />
tubes.<br />
Check for condenser refrigerant leaks.<br />
Check fluid temperature.<br />
Check sensor wiring <strong>and</strong> accuracy.<br />
Place the chiller in PUMPDOWN mode if the<br />
vessel is evacuated.<br />
155 OPTION SENSOR<br />
FAULT<br />
REMOTE RESET<br />
SENSOR<br />
155->Sensor Fault/Option<br />
Disabled:<br />
Remote Reset Sensor<br />
Check sensor resistance or voltage drop.<br />
Check for proper wiring.<br />
156 OPTION SENSOR<br />
FAULT<br />
AUTO CHILLED<br />
WATER RESET<br />
156->Sensor Fault/Option<br />
Disabled:<br />
Auto Chilled Water Reset<br />
Check sensor resistance or voltage drop.<br />
Check for proper wiring.<br />
157 OPTION SENSOR<br />
FAULT<br />
AUTO DEMAND<br />
LIMIT INPUT<br />
157->Sensor Fault/Option<br />
Disabled:<br />
Auto Dem<strong>and</strong> Limit Input<br />
Check sensor resistance or voltage drop.<br />
Check for proper wiring.<br />
158 SENSOR ALERT SPARE TEMPERATURE<br />
#1<br />
158->Spare Temperature #1<br />
[VALUE] exceeded limit of<br />
[LIMIT].*<br />
Check sensor resistance or voltage drop.<br />
Check for proper wiring.<br />
159 SENSOR ALERT SPARE TEMPERATURE<br />
#2<br />
159->Spare Temperature #2<br />
[VALUE] exceeded limit of<br />
[LIMIT].*<br />
Check sensor resistance or voltage drop.<br />
Check for proper wiring.<br />
160 DIFFUSER<br />
DIFFUSER<br />
160->Diffuser Position Alert; Check diffuser configuration in SETUP2<br />
ALERT<br />
POSITION<br />
Check Diffuser Configuration. screen.<br />
*[LIMIT] is shown on the CVC/ICVC as the temperature, pressure, voltage, etc., set point predefined or selected by the operator as an override,<br />
alert, or alarm condition. [VALUE] is the actual pressure, temperature, voltage, etc., at which the control tripped.<br />
84