10.04.2013 Views

Start-Up, Operation, and Maintenance Instructions

Start-Up, Operation, and Maintenance Instructions

Start-Up, Operation, and Maintenance Instructions

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

HFC-134a should not be mixed with air or oxygen <strong>and</strong><br />

pressurized for leak testing. In general, this refrigerant<br />

should not be present with high concentrations of air or<br />

oxygen above atmospheric pressures, because the mixture<br />

can undergo combustion.<br />

TESTING WITH REFRIGERANT TRACER — Use an environmentally<br />

acceptable refrigerant as a tracer for leak test<br />

procedures. Use dry nitrogen to raise the machine pressure to<br />

leak testing levels.<br />

TESTING WITHOUT REFRIGERANT TRACER — Another<br />

method of leak testing is to pressurize with nitrogen only<br />

<strong>and</strong> to use a soap bubble solution or an ultrasonic leak detector<br />

to determine if leaks are present.<br />

TO PRESSURIZE WITH DRY NITROGEN<br />

NOTE: Pressurizing with dry nitrogen for leak testing should<br />

not be done if the full refrigerant charge is in the vessel<br />

because purging the nitrogen is very difficult.<br />

1. Connect a copper tube from the pressure regulator on the<br />

cylinder to the refrigerant charging valve. Never apply<br />

full cylinder pressure to the pressurizing line. Follow the<br />

listed sequence.<br />

2. Open the charging valve fully.<br />

3. Slowly open the cylinder regulating valve.<br />

4. Observe the pressure gage on the chiller <strong>and</strong> close the<br />

regulating valve when the pressure reaches test level. Do<br />

not exceed 140 psig (965 kPa).<br />

5. Close the charging valve on the chiller. Remove the copper<br />

tube if it is no longer required.<br />

Repair the Leak, Retest, <strong>and</strong> Apply St<strong>and</strong>ing<br />

Vacuum Test — After pressurizing the chiller, test for<br />

leaks with an electronic halide leak detector, soap bubble solution,<br />

or an ultrasonic leak detector. Bring the chiller back to atmospheric<br />

pressure, repair any leaks found, <strong>and</strong> retest.<br />

After retesting <strong>and</strong> finding no leaks, apply a st<strong>and</strong>ing vacuum<br />

test. Then dehydrate the chiller. Refer to the St<strong>and</strong>ing Vacuum<br />

Test <strong>and</strong> Chiller Dehydration section (pages 50 <strong>and</strong> 53) in<br />

the Before Initial <strong>Start</strong>-<strong>Up</strong> section.<br />

Checking Guide Vane Linkage — When the chiller<br />

is off, the guide vanes are closed <strong>and</strong> the actuator mechanism is<br />

in the position shown in Fig. 37. If slack develops in the drive<br />

chain, do the following to eliminate backlash:<br />

1. With the chiller shut down <strong>and</strong> the actuator fully closed,<br />

remove the chain guard <strong>and</strong> loosen the actuator bracket<br />

hold-down bolts.<br />

2. Loosen guide vane sprocket adjusting bolts.<br />

3. Pry bracket upwards to remove slack, then retighten the<br />

bracket hold-down bolts.<br />

4. Retighten the guide vane sprocket adjusting bolts. Ensure<br />

that the guide vane shaft is rotated fully in the clockwise<br />

direction in order close it fully.<br />

Trim Refrigerant Charge — If, to obtain optimal chiller<br />

performance, it becomes necessary to adjust the refrigerant<br />

charge, operate the chiller at design load <strong>and</strong> then add or remove<br />

refrigerant slowly until the difference between the leaving<br />

chilled water temperature <strong>and</strong> the cooler refrigerant temperature<br />

reaches design conditions or becomes a minimum. Do<br />

not overcharge.<br />

Refrigerant may be added either through the storage tank or<br />

directly into the chiller as described in the Charge Refrigerant<br />

into Chiller section.<br />

72<br />

Fig. 37 —Guide Vane Actuator Linkage<br />

To remove any excess refrigerant, follow the procedure in<br />

Transfer Refrigerant from Chiller to Pumpout Storage Tank<br />

section, Steps 1a <strong>and</strong> b, page 70.<br />

WEEKLY MAINTENANCE<br />

Check the Lubrication System — Mark the oil level<br />

on the reservoir sight glass, <strong>and</strong> observe the level each week<br />

while the chiller is shut down.<br />

If the level goes below the lower sight glass, check the oil<br />

reclaim system for proper operation. If additional oil is required,<br />

add it through the oil drain charging valve (Fig. 2). A<br />

pump is required when adding oil against refrigerant pressure.<br />

The oil charge for the 19XR compressor depends on the compressor<br />

Frame size:<br />

Frame 2 compressor — 5 gal (18.9 L)<br />

Frame 3 compressor — 8 gal (30 L)<br />

Frame 4 compressor — 10 gal (37.8 L)<br />

Frame 5 compressor — 18 gal (67.8 L)<br />

The added oil must meet Carrier specifications for the<br />

19XR. Refer to Changing Oil Filter <strong>and</strong> Oil Changes section<br />

on page 73. Any additional oil that is added should be logged<br />

by noting the amount <strong>and</strong> date. Any oil that is added due to oil<br />

loss that is not related to service will eventually return to the<br />

sump. It must be removed when the level is high.<br />

An oil heater is controlled by the PIC II to maintain oil temperature<br />

(see the Controls section) when the compressor is off.<br />

The CVC/ICVC COMPRESS screen displays whether the<br />

heater is energized or not. The heater is energized if the OIL<br />

HEATER RELAY parameter reads ON. If the PIC II shows that<br />

the heater is energized <strong>and</strong> if the sump is still not heating up,<br />

the power to the oil heater may be off or the oil level may be<br />

too low. Check the oil level, the oil heater contactor voltage,<br />

<strong>and</strong> oil heater resistance.<br />

The PIC II does not permit compressor start-up if the oil<br />

temperature is too low. The PIC II continues with start-up only<br />

after the temperature is within allowable limits.

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!