10.04.2013 Views

Start-Up, Operation, and Maintenance Instructions

Start-Up, Operation, and Maintenance Instructions

Start-Up, Operation, and Maintenance Instructions

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Leave the oil charge in the chiller with the oil heater <strong>and</strong><br />

controls energized to maintain the minimum oil reservoir<br />

temperature.<br />

After Extended Shutdown — Ensure the water system<br />

drains are closed. It may be advisable to flush the water<br />

circuits to remove any soft rust which may have formed. This<br />

is a good time to brush the tubes <strong>and</strong> inspect the Schrader fittings<br />

on the waterside flow devices for fouling, if necessary.<br />

Check the cooler pressure on the CVC/ICVC default screen<br />

<strong>and</strong> compare it to the original holding charge that was left in<br />

the chiller. If (after adjusting for ambient temperature changes)<br />

any loss in pressure is indicated, check for refrigerant leaks.<br />

See Check Chiller Tightness section, page 48.<br />

Recharge the chiller by transferring refrigerant from the<br />

pumpout storage tank (if supplied). Follow the Pumpout <strong>and</strong><br />

Refrigerant Transfer Procedures section, below. Observe<br />

freeze-up precautions.<br />

Carefully make all regular preliminary <strong>and</strong> running system<br />

checks. Perform a Control Test before start-up. If the compressor<br />

oil level appears abnormally high, the oil may have<br />

absorbed refrigerant. Ensure that the oil temperature is above<br />

140 F (60 C) or above the cooler refrigerant temperature plus<br />

50° F (27° C).<br />

Cold Weather <strong>Operation</strong> — When the entering condenser<br />

water temperature drops very low, the operator should<br />

automatically cycle the cooling tower fans off to keep the temperature<br />

up. Piping may also be arranged to bypass the cooling<br />

tower. The PIC II controls have a low limit tower fan output<br />

that can be used to assist in this control (terminal 11 <strong>and</strong> 12 on<br />

ISM).<br />

Manual Guide Vane <strong>Operation</strong> — It is possible to<br />

manually operate the guide vanes in order to check control<br />

operation or to control the guide vanes in an emergency. Manual<br />

operation is possible by overriding the target guide vane<br />

position. Access the COMPRESS screen on the CVC/ICVC<br />

<strong>and</strong> scroll down to highlight TARGET GUIDE VANE POS. To<br />

control the position, use the INCREASE or DECREASE<br />

softkey to adjust to the percentage of guide vane opening that is<br />

desired. Zero percent is fully closed; 100% is fully open. To<br />

release the guide vanes to automatic control, press the<br />

RELEASE softkey.<br />

NOTE: Manual control overrides the configured pulldown rate<br />

during start-up <strong>and</strong> permits the guide vanes to open at a faster<br />

rate. Motor current above the electrical dem<strong>and</strong> setting, capacity<br />

overrides, <strong>and</strong> chilled water temperature below the control<br />

point override the manual target <strong>and</strong> close the guide vanes. For<br />

descriptions of capacity overrides <strong>and</strong> set points, see the Controls<br />

section.<br />

Refrigeration Log — A refrigeration log (as shown in<br />

Fig. 34), is a convenient checklist for routine inspection <strong>and</strong><br />

maintenance <strong>and</strong> provides a continuous record of chiller performance.<br />

It is also an aid when scheduling routine maintenance<br />

<strong>and</strong> diagnosing chiller problems.<br />

Keep a record of the chiller pressures, temperatures, <strong>and</strong> liquid<br />

levels on a sheet similar to the one in Fig. 34. Automatic<br />

recording of PIC II data is possible by using CCN devices such<br />

as the Data Collection module <strong>and</strong> a Building Supervisor.<br />

Contact a Carrier representative for more information.<br />

PUMPOUT AND REFRIGERANT<br />

TRANSFER PROCEDURES<br />

Preparation — The 19XR may come equipped with an<br />

optional pumpout storage tank, pumpout system, or pumpout<br />

compressor. The refrigerant can be pumped for service work to<br />

either the chiller compressor vessel or chiller condenser vessel<br />

by using the optional pumpout system. If a pumpout storage<br />

67<br />

tank is supplied, the refrigerant can be isolated in the storage<br />

tank. The following procedures describe how to transfer refrigerant<br />

from vessel to vessel <strong>and</strong> perform chiller evacuations.<br />

Always run the chiller cooler <strong>and</strong> condenser water pumps<br />

<strong>and</strong> always charge or transfer refrigerant as a gas when the<br />

chiller pressure is less than 30 psig (207 kPa). Below these<br />

pressures, liquid refrigerant flashes into gas, resulting in<br />

extremely low temperatures in the cooler/condenser tubes<br />

<strong>and</strong> possibly causing tube freeze-up.<br />

During transfer of refrigerant into <strong>and</strong> out of the optional<br />

storage tank, carefully monitor the storage tank level gage.<br />

Do not fill the tank more than 90% of capacity to allow for<br />

refrigerant expansion. Overfilling may result in damage to<br />

the tank or personal injury.<br />

Do not mix refrigerants from chillers that use different<br />

compressor oils. Compressor damage can result.<br />

Operating the Optional Pumpout Unit<br />

1. Be sure that the suction <strong>and</strong> the discharge service valves<br />

on the optional pumpout compressor are open (backseated)<br />

during operation. Rotate the valve stem fully<br />

counterclockwise to open. Front-seating the valve closes<br />

the refrigerant line <strong>and</strong> opens the gage port to compressor<br />

pressure.<br />

2. Ensure that the compressor hold-down bolts have been<br />

loosened to allow free spring travel.<br />

3. Open the refrigerant inlet valve on the pumpout<br />

compressor.<br />

4. Oil should be visible in the pumpout unit compressor<br />

sight glass under all operating conditions <strong>and</strong> during<br />

shutdown. If oil is low, add oil as described under<br />

Optional Pumpout System <strong>Maintenance</strong> section, page 75.<br />

The pumpout unit control wiring schematic is detailed in<br />

Fig. 35.<br />

TO READ REFRIGERANT PRESSURES during pumpout or<br />

leak testing:<br />

1. The CVC/ICVC display on the chiller control panel is<br />

suitable for determining refrigerant-side pressures <strong>and</strong><br />

low (soft) vacuum. To assure the desired range <strong>and</strong> accuracy<br />

when measuring evacuation <strong>and</strong> dehydration, use a<br />

quality vacuum indicator or manometer. This can be<br />

placed on the Schrader connections on each vessel (Fig.<br />

9) by removing the pressure transducer.<br />

2. To determine pumpout storage tank pressure, a 30 in.<br />

-0-400 psi (-101-0-2769 kPa) gage is attached to the storage<br />

tank.<br />

3. Refer to Fig. 29, 30, <strong>and</strong> 36 for valve locations <strong>and</strong><br />

numbers.<br />

Transfer, addition, or removal of refrigerant in springisolated<br />

chillers may place severe stress on external piping<br />

if springs have not been blocked in both up <strong>and</strong> down<br />

directions.

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!