Call switch, order no. 19 0708 00<br />

Connection on terminal, order no. 19 0700 x0, or display module, order no. 19 0700 80, or RAB,<br />

order no. 19 0701 00 (CONCENTO PLUS system)<br />

See table below<br />

Order no. 19 0700 x0<br />

or 19 0700 80<br />

or 19 0701 00<br />

Device Order no.<br />

Display module 19 0700 80<br />

RAB<br />

19 0701 00<br />

Terminal 19 0700 x0<br />

GND<br />

Reassurance light<br />

Call input<br />

+24 V<br />

BK<br />

YE<br />

WH(YE)<br />

RD<br />

IY(ST)Y 2x2x0.8 mm<br />

Call type*) Reassurance light Call input<br />

WC Call WL WR<br />

Call Bed 1 RL R1<br />

Call Bed 2 RL<br />

R2<br />

Call Bed 3 RL R3<br />

WC Call WL R3<br />

Call Bed 1 RL R1<br />

Call Bed 2 RL<br />

R2<br />

*) Note! Many inputs of the display module, RAB and terminals are configurable, i.e the<br />

call type can be changed. In addition there are further inputs available that are also<br />

configurable. For details, read the product leaflets accompanying the respective device.<br />

Several call buttons in the room<br />

Max. 4 call devices can be connected in line or star topology. The max. cable length per input is 20 m. The integrated 120 kOhm<br />

terminating resistor must be active for all call devices (= factory setting).<br />

Caution! Do not change the solder bridge 6. It must always be closed.<br />

00 8814 07, 10/12 (Rev. 2.0) 2<br />

<strong>Technical</strong> <strong>Manual</strong> Page 108<br />

GND<br />

RL<br />

RT<br />

+24 V<br />

Connector 7<br />

on switch<br />

Connection on terminal, order no. 10 0700 x0, or display module, order no. 10 0700 8x, or RAB,<br />

order no. 10 0701 x0 (Concento system)<br />

See table below<br />

GND<br />

Reassurance light<br />

Call input<br />

+24 V<br />

Order no. 10 0700 x0<br />

or 10 0700 8x<br />

or 10 0701 x0<br />

Device<br />

Display module<br />

RAB<br />

Order no.<br />

10 0700 80<br />

10 0701 00<br />

Display module 10 0700 85<br />

RAB<br />

10 0701 20<br />

Call type<br />

BK<br />

YE<br />

WH(YE)<br />

RD<br />

IY(ST)Y 2x2x0.8 mm<br />

GND<br />

RL<br />

RT<br />

+24 V<br />

Connector 7<br />

on switch<br />

Reassurance light Call input<br />

WC Call WL WR<br />

Call Bed 1 RL<br />

RT1<br />

Call Bed 2 RL<br />

RT2<br />

WC Call WL<br />

WR<br />

Call Bed 1 RL<br />

RT1<br />

Call Bed 2 RL<br />

RT2<br />

Call Bed 3 RL<br />

RT3<br />

Terminal 10 0701 x0 WC Call WL WR<br />

Call Bed 1 RL<br />

RT1<br />

Call Bed 2 RL<br />

RT2<br />

configurable RL R5<br />

Terminating resistor<br />

configurable RL R6<br />

Several call devices on one input can be connected in line topology. Star topology is not permissible. The maximum cable length<br />

per input is 15 m.<br />

The integrated 120 kOhm terminating resistor must be active in the case of the last call device at an input.<br />

The integrated 120 kOhm terminating resistor must be inactive in the case of all other call devices at the input.<br />

The terminating resistor is set to active at the factory. The terminating resistor is activated and deactivated via the solder bridge 6<br />

(see Fig. A).<br />

Solder bridge closed<br />

Terminating resistor active (factory setting)<br />

Solder bridge opened (e.g. with knife blade)<br />

Terminating resistor not active<br />

<strong>Tunstall</strong> <strong>GmbH</strong>, Orkotten 66, 48291 Telgte, www.tunstall.de