13.04.2013 Views

Technical Manual - Tunstall GmbH

Technical Manual - Tunstall GmbH

Technical Manual - Tunstall GmbH

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Management Interface, Order no. 19 0700 00<br />

Setting time and date<br />

1. Select “Time / Date” in the Main Menu.<br />

The “Time / Date” menu is displayed, see Fig. J.<br />

2. Select “Set Time”.<br />

The digit to be entered is flashing.<br />

3. Enter the current time.<br />

4. Select “Set Date”.<br />

The digit to be entered is flashing.<br />

5. Enter the current date using the format yyyy.mm.dd.<br />

6. To close the “Time / Date” menu, press Clear.<br />

Note! The time set here will be overwritten by the ConLog<br />

software.<br />

Note! The “Auto. daylight saving conversion” feature is currently<br />

not used. However, the daylight saving conversion is<br />

automatically performed by the ConLog software.<br />

Settings only with the service password<br />

If the Management Interface is connected to the ward bus, the<br />

menu item “Send time to System” must be changed from factory<br />

setting “Yes” to “No”.<br />

Paging module settings<br />

1. Select “Paging Module” in the Main Menu.<br />

The “Paging Module” menu is displayed, see Fig. K.<br />

2. Select „Paging Module ON/OFF“.<br />

The submenu “Paging Module ON/OFF” is displayed.<br />

3. Select “ON”, if a paging or a DECT system is connected.<br />

Select “OFF”, if no paging and no DECT system is connected.<br />

Sending a test message to a Pager or a DECT telephone<br />

1. Select “Test Message”.<br />

“Pager address” is displayed.<br />

2. Enter the pager address for the test message.<br />

3. Press Enter.<br />

The Test message “Testmessage“ is sent.<br />

4. To close the “Paging Module” menu, press Clear.<br />

Settings only with the service password<br />

If required the following factory settings can be changed: Baud<br />

Rate* (1200), Data Bits* (7), Stop Bits* (2), Parity* (Even),<br />

Timeout (500 ms), Retransmission* (9 min), Transmission At‐<br />

tempts (3), Polling Cycle (5 sec), Alias / Room No (Alias).<br />

* = The settings marked with a * will be overwritten by ConLog<br />

settings (“Project Configuration” menu).<br />

ConLog Interface<br />

If the Management Interface is connected to the group bus, the<br />

menu item “ConLog connection” must stay set to the factory set‐<br />

ting “Yes”.<br />

If the Management Interface is connected to the ward bus, the<br />

menu item “ConLog connection” must be changed from factory<br />

setting “Yes” to “No”:<br />

1. Select “ConLog Interface” in the Main Menu.<br />

The “ConLog Interface” menu is displayed, see Fig. L.<br />

2. Select “ConLog Connection”.<br />

The submenu “ConLog connection” is displayed.<br />

3. Select “OFF”.<br />

4. To close the “ConLog Interface” menu, press Clear.<br />

Note! For the standard baud rate (9600) the sync cycle must be<br />

changed to 3 sec in the Conlog II software. Higher baud rates<br />

can be used after consulting <strong>Tunstall</strong> <strong>GmbH</strong>.<br />

Set Time<br />

Set Date<br />

00 8814 00, 10/12 (Rev. 4.0) 4<br />

<strong>Technical</strong> <strong>Manual</strong> Page 130<br />

Time / Date<br />

Auto. daylight saving conversion<br />

15:23<br />

2011.07.31<br />

OFF<br />

Bus ConLog Tel. Paging<br />

Paging Module<br />

Paging Module ON/OFF<br />

Test Message<br />

ON<br />

Bus ConLog Tel. Paging<br />

ConLog Interface<br />

ConLog Connection<br />

ON<br />

Bus ConLog Tel. Paging<br />

<strong>Tunstall</strong> <strong>GmbH</strong>, Orkotten 66, D-48291 Telgte, www.tunstall.de

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!