Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
<strong>Tunstall</strong> <strong>GmbH</strong>, Orkotten 66, 48291 Telgte, www.tunstall.de<br />
Call switch with connection socket, order no. 19 0704 00<br />
Connection on terminal, order no. 10 0700 x0, or display module, order no. 10 0700 8x, or RAB,<br />
order no. 10 0701 x0 (Concento system)<br />
Device<br />
Display module<br />
RAB<br />
Terminating resistor<br />
Several call devices can be connected in line topolgy. Star topology is not permissible. The maximum cable length<br />
per input is 15 m.<br />
The integrated 120 kOhm terminating resistor must be active in the case of the last call device at an input.<br />
The integrated 120 kOhm terminating resistor must be inactive in the case of all other call devices at the input.<br />
The terminating resistor is set to active at the factory. The terminating resistor is activated and deactivated via the DIP switch or<br />
jumper 6.<br />
6<br />
Terminating resistor active (factory setting)<br />
= DIP switch ON (left) or<br />
= Jumper position left<br />
6<br />
Light switching<br />
24 V DC not from<br />
nurse call system<br />
GND<br />
Reassurance light<br />
See table below<br />
Call input<br />
+24 V<br />
Order no. 10 0700 x0<br />
or 10 0700 8x<br />
or 10 0701 x0<br />
Light<br />
230 V AC<br />
Order no.<br />
10 0700 80<br />
10 0701 00<br />
Display module 10 0700 85<br />
RAB<br />
10 0701 20<br />
Terminal 10 0701 x0<br />
Recommended pulse relays:<br />
Light switching - see below<br />
IY(ST)Y 2x2x0.8 mm<br />
Pulse relay<br />
BK<br />
YE<br />
WH(YE)<br />
RD<br />
IY(ST)Y 2x2x0.8 mm<br />
Call type Reassurance light Call input<br />
WC Call WL WR<br />
Call Bed 1 RL<br />
RT1<br />
Call Bed 2 RL<br />
RT2<br />
WC Call WL<br />
WR<br />
Call Bed 1 RL<br />
RT1<br />
Call Bed 2 RL<br />
RT2<br />
Call Bed 3 RL<br />
RT3<br />
WC Call WL WR<br />
Call Bed 1 RL<br />
RT1<br />
Call Bed 2 RL<br />
RT2<br />
configurable RL R5<br />
configurable RL R6<br />
LT1<br />
LT1<br />
GND<br />
RL<br />
RT<br />
+24 V<br />
Connector 7<br />
on switch<br />
Anti-surge diode<br />
min. 1N4007<br />
00 8814 10, 10/12 (Rev. 2.0) 3<br />
<strong>Technical</strong> <strong>Manual</strong> Page 118<br />
WH(YE)<br />
YE<br />
LT1<br />
LT1<br />
GND<br />
RL<br />
RT<br />
+24 V<br />
Connector 7<br />
on switch<br />
Terminating resistor not active<br />
= DIP switch OFF (right) or<br />
= Jumper position right<br />
Pulse relay (electronic): Pulse relay (mechanical*): Switching relay (mechanical) *):<br />
ELTAKO, ES60-TX60-24VDC<br />
ELTAKO, ES75-100-12..24 VDC<br />
SCHIELE entrelec TX60-24V<br />
BIAIG electronics TX60-24V<br />
ELTAKO, 1S9-24 VDC<br />
ELTAKO, S91-100-24 VDC<br />
Light button on pear push switch<br />
ELTAKO, R12-100-24 VDC (for DIN rail)<br />
ELTAKO, R91-100-24 VDC (Flush-mounted, surface-mounted version)<br />
FINDER, 49.61-7024.4050