3. Service<br />

Battery Set for UPS 60, Order No. 77 3450 00<br />

To ensure the safe function of the system, batteries should be replaced every 3 years - depending on<br />

the ambient temperature (Refer to diagram 1, Item 4). After 3 – 5 years, the battery capacity has<br />

dropped to approx. 60%.<br />

4. Battery service life<br />

The battery set UPS 60 comes with sealed, service-free and rechargeable lead-gel batteries VRLA.<br />

According to the EUROBAT classification, these batteries have a useful service life of 5 – 7 years.<br />

This time, however, strongly depends on the relevant ambient temperature. (Up to 20 °C: 7 – 8 years<br />

as shown in diagram 1)<br />

If the system will not be used for an extended period of time, the batteries should be fully charged to<br />

prevent a total discharge. (Refer to item 5 "Storage") While the system is not used, the battery fuse<br />

(located between the two batteries) has to be removed to prevent total discharge. After the charging<br />

process has been completed, the battery set for UPS 60 has to be disconnected from the power<br />

supply unit UPS 60 by disconnecting the battery connection cable (see chapter 2.) or by removing the<br />

battery fuse.<br />

Battery service life (years)<br />

Temperature<br />

Diagram 1: Battery service life in relation to ambient temperature<br />

4.1 Battery change<br />

Pb<br />

Lead-gel batteries contain harmful toxic substances. Observe valid safety directives when<br />

during handling and transport. For disposal, comply with local directives.<br />

Batteries bear the risk of excessive short-circuit currents. Never create any direct contact<br />

between the battery posts and or other conductive component parts. Therefore remove any<br />

wristband, watch, finger rings or other metal objects when working at the open unit. Always<br />

use tools with standard isolating handles.<br />

Batteries may be replaced only by the same type of battery (2 x 12 V; 24 Ah). We recommend the use<br />

of the battery type BAT 12-24, <strong>Tunstall</strong> Order No. 00 0648 87. The use of other makes may create<br />

problems due to different connecting terminals or differing dimensions.<br />

1. Shut off mains supply to the power supply unit UPS !!!<br />

2. Release the 6 fastening screws for the cover and remove the cover to the front.<br />

3. Confirm the position of the old batteries and after their removal, install the new batteries<br />

in the same manner.<br />

4. Make sure, the new batteries are in the same position and check for the correct battery<br />

contacts. False connections may damage the power supply unit UPS !<br />

5. Put the rubber grommets back on the connection screws.<br />

6. Fix the battery position by securing it with the Velcro tape.<br />