Power supply unit UPS, Order No. 77 3400 00<br />
The selected location must ensure sufficient air circulation above and below the unit. Therefore, check<br />
for minimum distance of 50 mm to walls, ceiling and other equipment. The venting ports must not be<br />
covered up. Insufficient air circulation may lead to damage to the power supply unit.<br />
Dimensional drawing:<br />
2. Connection<br />
The internal connection terminals are provided as screw/plug-in clamps.<br />
2.1 Mains connection<br />
You have to ensure, that the mains cable is disconnected from the AC supply voltage during the<br />
following procedure:<br />
1. Release 4 screws for the left cover and remove the cover to the front.<br />
Now, the terminal connection clamps are accessible.<br />
2. Direct the mains cable through the cable duct into the housing and connect to the appropriate<br />
terminal posts as designated in the unit.<br />
NOTE: To simplify this process, you may pull the input connector, connect the wires as shown and<br />
replace the plug in its socket.<br />
CAUTION ! Check for the correct and positive connection of the protective conductor.<br />
3. Secure the connecting cable against being pulled from the housing for example by fixing the<br />
installation cable with cable clamps.<br />
2.2 Output terminal clamps 24 V DC / 12.5 A<br />
The output voltage is generated via a primary pulse controller. This controller provides the output<br />
voltage of 24 V DC with 12.5 A current (for continuous operation considering all tolerance criteria).<br />
When in the normal operating mode, i.e. mains power supply, the electronic module monitors the<br />
output voltage. When the load current exceeds approx. 12.5 A, the output current is shut off (hicc-up<br />
mode) until the overload at the output terminal connections has been reduced.<br />
This is a self-correcting output voltage feature, as the output voltage will be reactivated. Further to this,<br />
the output voltage is protected by a 15 A flat fuse "F2".<br />
• The load shall be connected to the terminal clamps "+24V" and "0V" (provided 2 x).<br />
2.3 Control terminal clamps x + y<br />
The control terminal clamps "x" and "y" are used to prepare the unit for the uninterrupted power supply<br />
(UPS mode).<br />