Terminal SD6 P, order no. 19 0700 20<br />

Connect the connecting cable and set the DIP switches<br />

Note! There is no bridge between 1 and 2<br />

(GND) and no bridge between 3 and 4<br />

(+24V) in the connector. The bridges are on<br />

the printed circuit board.<br />

R6 = Door alarm<br />

R5 = Fire<br />

R4 = WC cancel button<br />

R7 = Door alarm<br />

Ward bus (data)<br />

Ward bus (speech)<br />

+24 V<br />

RD<br />

IA<br />

WH(YE)<br />

R6<br />

IB<br />

YE<br />

Legend:<br />

1 ) GND = Connection to Point 1 or 2 of the 4-pole connector,<br />

or Point 1 of the 10-pole connector<br />

2 ) Colour WA = WH. Only for Call & cancel switch only = WH(GN).<br />

3 ) Switching power per output: 100 mA at 24 V DC.<br />

00 8814 18, 10/12 (Rev. 2.0) 2<br />

<strong>Technical</strong> <strong>Manual</strong> Page 83<br />

+24 V<br />

ISA<br />

WH(GN)<br />

R5<br />

ISB<br />

GN<br />

BU<br />

GND<br />

+24 V<br />

ISC<br />

WH(BN)<br />

GND<br />

R4<br />

ISD<br />

BN<br />

BN<br />

+24 V<br />

+24 V<br />

AW<br />

WL<br />

RL<br />

GND<br />

10 9 8 7 6 5 4 3 2 1<br />

YE<br />

R3<br />

WH<br />

+24 V<br />

1 2 3 4<br />

Room lamp 3 )<br />

Power supply<br />

+24 V<br />

RD<br />

4-pole connector<br />

Max. wire cross section: 2.5 mm 2<br />

R2<br />

BK or BU<br />

+24 V<br />

R1<br />

1 2 3 4 5 6 7 8 9 10 11 12<br />

WH<br />

BK or BU GND 1 )<br />

BK or BU GND 1 )<br />

BK or BU GND 1 )<br />

Inputs<br />

A maximum of 4 monitored devices can be connected at each<br />

input.<br />

All inputs are configurable. For restrictions when installing in an<br />

existing Concento system, see the ”Configuring inputs” chapter.<br />

The factory setting is shown in Fig. D and E.<br />

The following parameters can be configured:<br />

- Call type<br />

- NC/NO contact<br />

- Static call (trigger pulse) / dynamic call (trigger duration)<br />

RD<br />

WH<br />

RD<br />

WH 2 )<br />

RD<br />

WH<br />

YE<br />

RD<br />

YE<br />

WH<br />

RD<br />

WH<br />

GND 1 )<br />

GND 1 )<br />

GND 1 )<br />

ON<br />

OFF<br />

BK or BU<br />

BK or BU<br />

12-pole connector<br />

BK or BU<br />

R1 = Call button Bed 1<br />

R2 = Call button Bed 2<br />

R3 = WC call button<br />

10-pole connector<br />

DIP switch<br />

ON: Terminal is the first or last bus<br />

user on the ward bus<br />

(= bus termination)<br />

OFF: Terminal is neither the first nor<br />

last bus user on the ward bus<br />

One wire<br />

Four wires<br />

Factory setting of the inputs<br />

Inp. Call type NC or NO<br />

contact<br />

Output<br />

Input<br />

Static or<br />

dynamic call<br />

R1 Bed 1<br />

NO contact Static call<br />

R2 Bed 2<br />

NO contact Static call<br />

R3 WC call<br />

NO contact Static call<br />

R4 WC cancel button NO contact Static call<br />

R5 Fire<br />

NO contact Dynamic call<br />

R6 Door alarm NO contact Static call<br />

R7 Door alarm NO contact Static call