CONCENTO PLUS - <strong>Technical</strong> <strong>Manual</strong>, 11/12 (Rev. 3.0), 00 8814 14<br />

3. Room types<br />

Frequently used room types are explained in the following pages on the basis<br />

of equipment examples.<br />

3.1 Cables legend<br />

The following letters are used for cables in the room type plans:<br />

Code Cable type Area of use<br />

a IY(ST)Y 2x2x0,8 - Secondary lines (except switches with 2 buttons,<br />

e.g. Call & cancel switch/WC)<br />

- Ward bus without speech (minimum requirement)<br />

- Group bus without speech (minimum requirement)<br />

c IY(ST)Y 4x2x0,8 - Ward bus with or without speech<br />

- Group bus with or without speech<br />

- Secondary lines to switches with 2 buttons, e.g.<br />

Call & cancel switch/WC<br />

k NYM 2x2,5 mm2 or<br />

NYM 2x1,5 mm2 or equivalent<br />

Power supply, equipotential bonding<br />